Gree TD GUD 30/01 Manual de instalación - Página 7
Navegue en línea o descargue pdf Manual de instalación para Pasarela Gree TD GUD 30/01. Gree TD GUD 30/01 12 páginas. For u-match r32 units
RS485 network topology must be arranged as bus (point to point), connection to
star, ring or triangle is not possible !!!
Maximal length of RS485 line is 500 meters.
The rst and the last device on the bus should have terminating resistor 120
tween A and B lines. (some devices do already have this implemented inside, it can be
activated by DIP-switch or by software command - see manual to speci c device)
Meeting these requirements is essential for seamless communication, partic-
ularly in environments with high surrounding electromagnetic interference (i.e.
substations, server rooms, utility rooms).
RS485 cable requirements
Installation manual
be-
7