Gamewell BDT-SS Manual rápido - Página 3

Navegue en línea o descargue pdf Manual rápido para Alarma de humo Gamewell BDT-SS. Gamewell BDT-SS 4 páginas. Single-ended, reflected-type, addressable beam smoke detector with smartscan

Wiring
Diagram
Switch
Locations
Wiring Diagram (with RTS451/KEY)
BD-SS and BDT-SS
CS-2516
BD-SS / BDT-SS
09/01/06
Specifications
Environmental Specifications
Temperature
–22°F to 131°F (–30°C to 55°C).
Humidity
10 – 93% RH noncondensing.
Electrical Specifications
Voltage
15 to 32 VDC.
Average standby current
24 VDC: 2 mA maximum (LED flashing,
SLC @ 24 V).
LED current
6.5 mA maximum.
Remote annunciator current
11.2 mA maximum.
Average current during testing
500 mA maximum.
Alarm current
24 VDC; 8.5 mA maximum (LED on).
Trouble/fault current
24 VDC; 4.5 mA maximum (LED on).
Fault condition current
Add to standby current; 100 mA
maximum.
Alignment mode current
24 VDC; 20 mA maximum.
External supply (BDT-SS only)
Voltage: 15 to 32 VDC.
Current: 0.5 A maximum.
Remote output (alarm)
Voltage: 15 to 32 VDC. NOTE: Output
voltage is the same as device input voltage.
Current: 15 mA maximum, 6 mA
minimum. NOTE: Output current is limited
by 2.2K ohm resistor.
Heater kit BEAMHK
Voltage: 15 to 32 V. Current: 92 mA
maximum @ 32 V (heater only).
Power consumption: nominal 1.6 W
@ 24 V; maximum 3.0 W @ 32 V.
Heater kit BEAMHKR
Voltage: 15 to 32 V. Current: 450 mA
maximum @ 32 V (per reflector). Power
consumption (per reflector): nominal 7.7
W @ 24 V; maximum 15.0 W @ 32 V.
Mechanical Specifications
Detector dimensions
10.0" H x 7.5" W x 3.3" D
(254 mm H x 191 mm W x 84 mm D).
Reflector dimensions
For 16' to 230' (5 to 70 m) applications:
7.9" x 9.1" (200 x 230 mm).
For applications beyond 230'/70 m:
15.7" x 18.1" (400 x 460 mm).
Page 3 of 4