aguilera electronica AE/C5-OP Manual de inicio rápido - Página 2

Navegue en línea o descargue pdf Manual de inicio rápido para Alarma de humo aguilera electronica AE/C5-OP. aguilera electronica AE/C5-OP 2 páginas. Photoelectric smoke detector

Installing the head
Align the components as show in the Figure.
Mate the detector head into the base and twist clockwise to secure it.
In case that detector head is not matching marks with the base the
detector will operate but connection polarity of remote LED annunciator
are changed and then it is not assured its well perfomed operation.
The maximum number of detectors installed in the same loop is 30 units.
After all detector have been installed apply power supply to the detector
loop.
CAUTIONS.
To prevent detector from dirty effect and warranty cancellation, the
smoke detector must remain covered until the area is clean and dust
free.
Detector protection cover is not intended to provide complete protection
against dust ambient pollution, therefore detector should be removed
before beginning to made masonry works, inner space revamping or
other dust producing activity.
Do not paint any part of detector because paint can close air entry holes and then detector operation will be affected.
Detector protection cover must be removed before fire detection system can be made operational.
TESTING.
Detectors must be tested after installation and following periodic maintenance.
Before testing, notify to the proper authorities that the detector system is undergoing maintenance, and be sure that all required functions related
to alarm emergency exit, extinguishing system and automatic extinguishing shoot in are cancelled.
Check that when you remove each detector from the base the fire alarm panel will be move announcing zone fault notice. If no any fault is
coming then recheck that there are not placed 2 wires or more at the same detectors base clamp at the terminal block.
Check to see if the indicator green LED is flashing every 3~5 seconds. If green LED fails to flash, it indicates the detector non-foperation
condition or a faulty wiring is made.
Apply some smoke sample from a test smoke aerosol to each detector during at least 10 seconds to activate the detector-sensing
chamber. When sufficient smoke portion has entry within the chamber then detector will generate an alarm signal being recognized
externally by a continuous lighting from two external LEDs and fire alarm panel shall be in alarm mode.
If a remote LED annunciator is coupled then also shall be light activated. If lighting activation does not arrive checking for wiring and well
done detector plug-in into base is required to be done it again
To made same detector testing as above mentioned for another selected detector placed at the same detection loop, first at all you shall
reset the loop by switching-off from the remote fire alarm panel and also chek the zone is in stand-by mode before start-up with the next one
detector checking.
All detectors not capables to perform testing as above indicated must be replaced for technical service attendance.
After testing implementation the alarm emergency exit, extinguishing system and automatic extinguishing shoot in functions cancelled previously
at the fire alarm panel shall be activate and proper authorities shall be informed that the fire alarm system is again in operation.
DETECTOR MAINTENANCE GUIDELINE.
The recommended minimum requirement for detector maintenance consists of an annual cleaning of dust from the detector head using a vacuum
cleaner. All ambient head detector entry holes shall be keeping totally cleaned from ambient entry obstacles. For an exhaustive clean traitment
the detector head should be send to AGUILERA ELECTRONICA, Customer Assistance Department.
Do not attempt to disassemble factory sealed detector head. Opening the detector head the detector warranty will be void.
SPECIFICATION.
DC:PowerSupply
Standby current:
Alarm current:
Loop Wires sizes:
Operating Temperature Range:
Operating Humidity Range:
Start-up Time (Max.):
Lighting Annunciators:
Remote alarm output, rate:
Detector Dimensions:
Raw Material:
Ae-man-320-0.0 v1.1
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
15 ~ 35 Vdc
35 µA
70 mA max.
2
2 X 1.5 mm
10ºC a +50º C ambient dry temperature.
10% al 90% Relative Humidity, Non-condensing.
60 s
Standby:
Leds flashing once every 3~5 seconds.
Alarm:
Continuous red lighting from LEDs
Remote LED annunciator, 6 Vdc.
Cover :
Cover Height with base:
White ABS plastic.
Phone.:+34 91 754 55 11 www.aguilera.es
BASE DETECTOR
1º ALING WITH SHORT MARK
AND PLACE THE DETECTOR
INTO THE BASE
HEAD DETECTOR
99 mm. (Diameter)
46 mm.
2º TWIST CLOCKWISE
TO ALIGN WITH TWO
LONG MARKS
0832
0832-CPD-0203
LPCB Nº 512a/02
EN 54-7:2000
TECHNICAL MANUAL
2