DECODE EMU Series Manual del usuario - Página 11

Navegue en línea o descargue pdf Manual del usuario para Instrumentos de medida DECODE EMU Series. DECODE EMU Series 15 páginas. Electricity measurement units

EMU - User manual v1.2
5.1.3

Function Error

In the event of an error, the following response is returned.
Byte
Field name
1
Device address
2
Function
3
Error code
4
Register address Low
5
Register number Hi
Error code may have folowing values:
1 - Function code not supported
2 - Reading registers out of range (> 40017)
3 - Number of registers out of range (> 17)
4 - Function execution error
www.decode.rs
Content
x
8
1, 2, 3 or 4
x
x
11/15
Modbus communication
EMU_UM_V12_05042020.pdf