Airflow Uno hab Kit de instalación - Página 8
Navegue en línea o descargue pdf Kit de instalación para Sistema de calefacción Airflow Uno hab. Airflow Uno hab 16 páginas. Cavity wall decentralised mechanical ventilation with heat recovery unit
También para Airflow Uno hab: Manual de instrucciones de instalación y funcionamiento (16 páginas), Instrucciones (2 páginas), Manual de mantenimiento (2 páginas)
CHAPTER 5
WALL
INSTALLATION
m
WARNING
© Airflow - we reserve the right to make changes without prior notice
5.0
Installation
The following must be read and followed before installation work or before opening the electrical terminals
compartment. Isolate the device from the mains power supply and secure against being switched on again.
– Installation of one ventilation unit
The following minimum clearances to walls and ceilings must be observed when positioning the ventilation unit or
core hole for the wall installation sleeve (see Fig. 3).
All dimensions in mm
– Installation of two ventilation units
The following minimum clearances must be observed when positioning two ventilation units or the core hole for the
wall installation sleeves in order to prevent short-circuiting (see Fig. 4).
All dimensions in mm
INSTALLATION PREPARATION:
– The unit installation requires a core hole
• Ø 162 mm core hole at an 1-2 deg. angle, downward towards outside
• or Ø 172 mm horizontal core hole (condensate wedge to be used on wall sleeve).
Alternatively, for new build installations, the Unohab Brickwork template blocks 365mm/490mm (Part no:
90001000; 90001001) can be used for the core hole.
– Place empty conduit in the wall channel ready for the electrical connection cable. The empty conduit must
be placed below the core hole (see Fig. 3 & 4)!
Unohab Cavity Wall Installation Kit
8
Installation and Operating Instructions
Fig .3
Fig .4