CEP 6503GU Instrucciones de instalación y funcionamiento - Página 2

Navegue en línea o descargue pdf Instrucciones de instalación y funcionamiento para Unidad de distribución de energía CEP 6503GU. CEP 6503GU 3 páginas. Temporary branch power distribution unit with ground fault protection for personnel

T E S T P R OC E DUR E
All Models
Connect the temporary power distribution unit to
an appropriate power source.
1. Verify all circuit breakers are in the "on"
position.
2. Push the test button on the individual GFCI
module. The unit should trip.
3. Push the reset button. The indicator light
should come on.
4. Repeat steps 2 & 3 for the remaining module.
T R OUB LE S HOOT ING
The GFCI Modules within the temporary power
distribution unit will trip whenever one or more of
the following abnormal conditions exist in the line
(supply) side circuit:
1. Either line (hot) conduct or is transposed with
the neutral conductor.
2. Either line (hot) conductor is open
(disconnected)
3. There is an excessive voltage imbalance
between line 1 and line 2 circuits. This may be
the result of an open neutral conductor in the
supply circuit.
When the abnormal condition(s) in the supply
circuit is corrected, the unit may be reset for
normal use by completely removing and then
reapplying line power. It is recommended that
the GFCI test procedure be repeated at this time.
When a GFCI module trips,
pressing the reset switch, being careful to look
for possible danger to personnel. If the module
resets, the fault was momentary and has
cleared. If it trips again immediately, the fault is
still present and the GFCI module is perfo
its safety function. To locate the fault, disconnect
all loads and again try pressing the reset switch.
The module should reset. Reconnect the loads
one at a time. The module will trip when the
faulted load is reconnected. Inspect all tools,
applian ces and extension cords in the faulted
load circuit, repairing or replacing any that are
not in good condition.
Ph: 800-474-7570, 602-272-8128 Fax: 602-272-8014
www.BestMaterials.com Email: [email protected]
NOT E : Tripping of a circuit breaker in these
models can only result from an overload or short
circuit condition in its individual load circuit.
When the fault in the load circuit is corrected or
removed, the circuit breaker can be reset for
normal use by switching handles to "OFF"
position and then to the "ON" position.
NUIS ANC E T R IP P ING
All cables have some capacitive leakage. In a
120 volt system, there is a li mited to the length of
to ground will build up causing a GFCI to trip.
Individual 120 volt branch circuit load cords
should be limited to 250 feet in length.
AP P LIC AT ION NOT E S
Enclosure is a NEMA Type 1, co
indoor use to provide a degree of protection to
personnel against access to hazardous parts
and to provide a degree of protection of the
equipment inside the enclosure against ingress
of solid foreign objects (falling dirt).
HIG H V OLT AG E LIG HT
An illuminated high voltage light indicates the
input wiring is incorrect ; check the power source.
C ONT AC T MONIT OR LIG HT
The red monitor light is a welded contact
indicator. If the monitor light is on with the unit
attempt to reset it by
tripped, it indicates the contact is welded, and
the unit should be replaced immediately -- there
is no GFCI protection . When the TEST button is
pressed, both the POWER light and MONITOR
light should go out, and come back on when the
rming
RESET button is pressed.
nstructed for