6.1 Electrical connection
As standard, EPO-V series electric heaters include a terminal block for connecting one power supply cable and one or
two cables with control signal (see the figure).
When the electric heater is used together with a DUPLEXVENT unit with built-in control, this control ensures that all
conditions for the safe operation of the heater are met.
When the electric heater is used together with a DUPLEXVENT unit without built-in control, its operation is allowed only
when all conditions for its commissioning are met.
7 .
C o m m i s s i o n i n g
Before commissioning the appliance, the following must be ensured:
Check whether all instructions from the above chapters were observed during the installation of the appliance and its
●
connection to the mains supply or control systems.
The operating temperature of the device is up to +40 ° C at a relative humidity of up to 80 %.
●
Check whether the minimum air flow through the appliance is maintained in all operating modes of the air-handling
●
system. The minimum air flow rate is specified on the identification plate of the appliance.
Check the correct setting of the run-down time of the fan that transports air through the appliance. The fan run-down
●
time is specified on the identification plate of the appliance.
Set the air-handling system in such a way so that return air flow through the appliance does not occur in any
●
operating mode.
Ensure sufficient filtration of air being heated, also for periods when the appliance is out of operation. The filtration
●
class for air being transported must be at least G4 or higher.
The appliance must always be connected to the supply voltage via recommended protection. The protection rate is
●
specified on the identification plate of the appliance.
Carry out an initial electrical inspection as per applicable standards. A written record of this inspection must be
●
made.
ATTENTION:
The surface temperature of the appliance reaches up to 70 ° C during operation (switching element coole rs), after
switch-off it can temporarily reach up to 120 ° C. I t is therefore necessary to take extra care. A safety warning sign is
provided to warn of the danger of burning.
The person commissioning the appliance must ensure the training of operating personnel and hand this manual over to
them.
8 .
O p e r a t i o n a n d m a i n t e n a n c e
The maintenance of the electric heater must be carried out in compliance with the operating instructions and suitable
means of access to the air-handling system must be used (ladders, mobile steps, platforms etc.).
The inspection and maintenance of the electric device is carried out in accordance with applicable electric regulations
and local operating instructions compiled by the user. The user must arrange for the regular electrical inspections of the
electric appliance at set intervals in accordance with applicable standards.
6