NO.5
Functions & Settings
1. FACTORY SET: Factory set includes system type, compressor protect, emergency heat mode and
change over.
2. SYSTEM TYPE: The thermostat supports up to 8 types(from 00 to 07) of heating and cooling
combined system.
3. COMP PROTECT: Time delay to start the compressor. Range: 00~10minutes.
4. EM HEAT MODE: Emergency heat mode ON: When it is set to ON, the thermostat can start EM HEAT
under mode bar. EM HEAT is especially for the situation when the compressors have risk to work.
5. CHANGE OVER: change over for heat/cool mode automatically. ON: During AUTO mode, the
thermostat will change to HEAT or COOL automatically. OF: The thermostat does not change
HEAT/COOL automatically in AUTO mode.
No.
Terminals need to be connected
00
C, RC, Y1, G
01
C, RH, W2, G
02
C, RC, Y1, W2, G
03
C, RC, Y1, W1, G
No.
Terminals need to be connected
04
C, RH, Y1, W1, W2, G
05
C, RH, Y1, Y2, W1, W2, G
06
C, RH, Y1, W1, G, W2
07
C, RH, Y1, Y2, W1, G, W2