E-T-A CPC12EN-T1-001 Manual de inicio rápido - Página 2

Navegue en línea o descargue pdf Manual de inicio rápido para Controlador E-T-A CPC12EN-T1-001. E-T-A CPC12EN-T1-001 7 páginas. Bus controller

CPC12EN bus controller
Technical data (T
Operating voltage U
B
Reverse polarity
protection
Quiescent current I
0
Supply via contact lever or additionally
XD1 terminal
(push-in)
Wire stripping length
EtherNet/IP interface (XF1, XF2)
RJ45
Ethernet interface (X1)
RJ45
IP reset
Momentary switch
Dimensions
(H x W x D)
Mass
System components
EM12-T supply module
Bus controller
Circuit protectors can
be mounted side-by-
side
Visual operation status indication
by means of multicoloured LED
Operating mode
Supply voltage OK
Firmware update
Actuator voltage OK
No actuator voltage
No device connected
or bus error
Operating mode
No IP address
Valid IP address, no
CIP connection
Active CIP connection green
CIP connection time
exceeded
Double IP address
7
detected
Operating mode
Ready to communicate green
Internal configuration
Critical error recoverable red blinking
Critical error not
recoverable
2
= 25 °C, U
= V)
amb
B
DC 24 V (18 ... 30 V)
yes
typically 75 mA
0.2 mm
2
to 1.5 mm
2
AWG24 – AWG14 str.
8 mm
Connection to Ethernet/IP bus system.
When wiring and connecting to the
Ethernet IP bus system the installation
and wiring regulations of the EtherNet/
IP™ specification have to be observed.
Communication interface to web server
Reset IP address
(interface X1) by pushing the
momentary switch for min. 3 sec
23 x 80 x 98.5 mm
(tolerances to DIN ISO 286 part 1 IT13)
approx. 70 g
Types
EM12-T00-000-DC24V-40A
CPC12xx-Tx-xxx
REX12D-T
REX22D-T
Indication of operating mode
LED US1
LED US2
green
---
off
off
green
green
green
red
green
orange blinking
Indication of operating mode
LED NS (network status)
off
green blinking
red blinking
red
Indication of operating mode
LED MS (module status)
green blinking
red
ControlPlex
(
Technical data (T
Visual signalling of RJ45 interfaces
LED LNK
Operating mode
Link available
No link available
LED ACT
Operating mode
Activity available
No activity
General data
Housing material
Mounting method
Ambient temperature
(TAMB)
Storage temperature
Mounting temperature +5 °C ... +60 °C
Damp heat
Altitude
Operation pressure
Vibration resistance
Degree of protection
EMC requirements
(EMC Directive, CE
Logo)
Insulation co-
ordination (IEC 60664)
Instructions for
installation
www.e-t-a.de
®
)
= 25 °C, U
= V)
amb
B
Indication of operating mode
green
off
Indication of operating mode
orange blinking
off
Plastic material
Symmetrical rail to EN 60715 - 35 x 7.5
-30 °C ...+ 60 °C
(without condensation, cf. EN 60204-1)
-40 °C ... +70 °C
96 hrs / 95% RH RH/40 °C to IEC 60068-
2-78-Cab climate class 3K3 to EN 60721
2,000 m above sea level
3,000 m above sea level up to +55 °C
4,000 m above sea level up to +50 °C
4 bar above atmospheric pressure
5 g, test to IEC 60068-2-6 test Fc
IP20
Emitted interference: EN 61000-6-3
Noise immunity:
EN 61000-6-2
Overvoltage category II/
pollution degree 3
Mounting or actuation of the REX
connector arm must only be effected
at dead-voltage. For start-up the REX
connector arm must be closed.
2116