Mounting examples for ESX10-T
LINE+ busbar
X22261102 grey
or X222611xx
signal bar
X22200503 grey
or X222005xx
or
jumper
X22200513 grey
remove protection
against brush contact
from bottom side
insert busbars
and protection slides
to be flush with housing sides
insert signal bars to
be flush with housing
and place them centrally
over the contacts
Mounting procedure:
Before wiring insert busbars into protector block.
Max. 10 insertion/removal cycles for busbars.
Recommendation:
After 10 units the busbars and signal busbars should be interrupted and receive a new entry live
Table of lengths for busbars
(X 222 611 02 / X 222 005 03 or cut off, see accessories)
No. of units
Length of busbar (mm) ± 0.5 mm
continuous busbar
500 mm length, cut
0 V busbar
X22261102 grey
or X222611xx
2
3
4
22
34.5
47
(12.5 x n)-3 = length of busbars ± 0.5
e. g. (12.5 x 5)-3 = 59.5 ± 0.5
insert protection
against
brush contact
12.5 x n = width of protector block
e. g. 12.5 x 5 = 62.5
5
6
59.5
72
84.5
- 5 -
5 ESX10-TA
with busbars
5 ESX10-TB
with busbars
and jumpers
7
8
9
97
109.5
10
122