Kohler 36VDC Manual de instrucciones de instalación - Página 21

Navegue en línea o descargue pdf Manual de instrucciones de instalación para Generador portátil Kohler 36VDC. Kohler 36VDC 44 páginas. Dc generator sets

Kohler 36VDC Manual de instrucciones de instalación
Figure 1-18
1
1. To positive (+) terminal on starter solenoid.
2. To ground (–) terminal on or near starter motor.
Figure 1-18 Typical Battery Connection
1.9.1
Engine Starting Battery Installation
Procedure
Use the following procedure to install and connect the
generator set engine starting battery.
1. Ensure that the starting battery is fully charged
before placing the battery in service.
2. Clean the battery posts and/or adapters if
necessary.
3. Install the battery post adapters, if needed.
4. Place the battery inside the housing.
5. Connect the positive (+) lead to the engine
starting battery.
6. Connect the negative (–) lead to the engine
starting battery.
Refer to the generator set operation manual and the
battery
manufacturer's
maintenance instructions.
When power is applied to the VSC controller (that is,
when the battery is connected), you will be prompted
to set the date and time, and then to set the exerciser.
See
the
generator
instructions.
If the battery is disconnected for service or
replacement, the exercise settings on the VSC
controller are lost. Set the exerciser after installing
and connecting the battery.
TP-6842 7/15
2
KPS_030
instructions
for
battery
set
operation
manual

1.10 Generator Set Accessories

Have
accessories
distributor/dealer or a licensed electrician. Follow the
installation instructions provided with each kit. Use
separate conduit for AC and DC leads to reduce the
possibility of electrical interference.
leads and conduit do not interfere with the operation of
the generator set or obstruct the service areas. Verify
that the electrical installation complies with the
National Electrical Code (NEC) and all applicable local
codes.
See Section 2, Wiring Diagrams, for more
information
regarding
connections.

1.10.1 Carburetor Heater

An optional carburetor heater is recommended for
improved cold starting in locations where the ambient
temperature drops below 0°C (32°F). The carburetor
heater prevents condensation and carburetor icing.
The heater turns on when the temperature at the
thermostat falls below approximately 4°C (40°F) and
turns
off
when
approximately 16°C (60°F). The carburetor heaters
are shown in Figure 1-19.
To install the carburetor heater, follow the instructions
provided with the kit. Figure 1-20 shows the installed
carburetor heater kit installed for a 6 kW generator set.
The heater requires a continuous source of power.
Plug the carburetor heater into the 120 VAC
receptacle provided.
Figure 1-19
1
for
1. Power plug
2. Thermostat
3. Heater
Figure 1-19 6VSG Carburetor Heater
installed
by
an
authorized
Verify that the
generator
set
the
temperature
rises
2
Section 1 Installation
electrical
above
3
KPS_041