Solution: Connect the connectors properly, the swapping does not damage the equipment.
- When the adapter has been connected, yellow and, in some cases, green LEDs are lighted on EnergyBank, the
back-up equipment is supplied.
Cause: An unsuitable type of adapter, insufficiently low output voltage or current. This situation may happen
whenever EnergyBank is used with a unit other than a GSM gateway and available adapter.
Solution: Use a suitable adapter, the adapter output voltage must be in the whole range of load within the limits
included in the "Technical Parameters" section, the adapter current must be 200mA higher at least than the
maximum power consumption.
- EnergyBank has a substantially lower capacity during back-up despite of having been fully charged.
Cause 1: The usable capacity of accumulators decreases at higher discharge currents.
Cause 2: A deteriorated capacity of accumulators due to ageing.
Solution: Replace the accumulators.
- EnergyBank turns off when the backed-up equipment is turned on in the back-up mode.
Cause: The inrush current following the equipment turn-on made the accumulator voltage drop and EnergyBank
turns off.
Solution: Keep the equipment connected to EnergyBank continuously, never switch the backed-up equipment in
the back-up mode.
7. Technical Parameters
Input voltage:
11.5 to 14.5V
Pass-through loss at mains supply:
max. 0.5V
Maximum output current:
adapter output current minus 200mA, max. 1A
Accumulators used:
NiMh, size AA, 1800mAh, 10 pcs.
Self-consumption - off status:
30uA
Self-consumption - back-up status:
15mA
Self-consumption - charging:
max. 200mA
Charging current:
60 to 200mA (according to the battery charging level)
Accumulator voltage for low power:
11.3V
Accumulator voltage for turn-off:
10V
Dimensions:
170x130x45mm
Operational temperature:
0 to 45°C
EasyGate operation time in EnergyBank back-up mode (applies to new accumulators):
- Standby mode (70mA)
approx. 20 hours
- GSM in connection (200-300mA)
approx. 6 hours
Warranty for this device is 24 month, not valid for accumulators
___________________________________________________________________________________________

EC Declaration of Conformity

Directive: Electromagnetic compatibility
(EMC): 89/336/EEC
Manufacturer:
2N TELEKOMUNIKACE a.s.
Modřanská 621
143 00 Prague 4
Czech Republic
Declares that the product:
®
ATEUS
- EnergyBank
®
Type numbers: ATEUS
– EnergyBank,
501399E
Description: Backup power supply
© 2005, 2N TELEKOMUNIKACE a.s. – Praha, PS 1174 v.1.0
Designed for: Backup power supply for 12V
powered devices
Conforms to the following Standards:
EMC: EN 55 024:1998, A1:2001, A2:2003
EN 55 022:1998, A1:2000, A2:2003,
A1/Cor.:2003, Cor.:2003
Date and place of issue:
Prague, Czech Republic, 17.3.2005
Manufacturer's stamp
...................................................
............................
Ing. Oldřich Stejskal, executive director
EnergyBank - Instructions for Use
1. Purpose
EnergyBank is designed to back up accidental supply voltage outages for equipment supplied with 12 V dc
voltage with the peak current drain of 1A. The backed-up power supply works as a pass-through system, i.e. the
backed-up equipment is connected continuously to the output connector and the power supply (typically a mains
adapter) to be backed up is connected to the input connector. During a voltage failure on the input connector,
EnergyBank transits automatically into the back-up mode.
Primarily, EnergyBank is designed to back up EasyGate and SmartGate GSM gateways made by 2N
TELEKOMUNIKACE (hereinafter referred to as GSM gateways). The backed-up power supply is connected
between the mains adapter and the GSM gateway, the adapter being included in the GSM gateway delivery.
- When a device other than a 2N gateway is used for back-up, it is necessary to observe the parameters included
in the "Technical Parameters" section. Especially, be sure to use an appropriate mains adapter. The adapter
voltage must be within the input voltage limits mentioned in the Technical Parameters; common transformer
adapters usually do not meet these requirements. The use of an unsuitable adapter may lead to a substantial
reduction of the battery life or equipment damage. You can purchase a suitable adapter with stabilised output
voltage from the 2N company.
- When your EnergyBank outlives its usefulness, dispose of it in accordance with applicable legal regulations.
2. Delivery Contents
- a backed-up power supply base board, including accumulators;
- screws and dowels for wall mounting;
- an EnergyBank - backed-up equipment interconnecting cable;
- a mounting pattern template and Instructions for Use.