AVLELEC ULS Series Hoja de instalación
Navegue en línea o descargue pdf Hoja de instalación para Altavoces AVLELEC ULS Series. AVLELEC ULS Series 2 páginas. Fire protective signaling speaker
Installation - Series ULD (28LO) Fire Protective Signaling Speaker
These speakers are intended to be employed in either of the following configurations:
A. For fire alarm signaling service in conjunction with a compatible Listed system control unit, the
combination of which is intended to be installed as a combination system control in accordance
with the applicable requirements of NFPA 72 and the local authorities having jurisdiction. The
amplifier, in conjunction with the tone generator located in the control unit, provides the power and
signal, either for the alarm evacuation and/or for voice communication.
B. For general (non-fire alarm) signaling service in conjunction with compatible Listed sound
recording and reproducing equipment, the combination of which is intended to be installed in
accordance with the applicable requirements of the National Electrical Code and the local
authorities having jurisdiction. The amplifier or other sound reproducing equipment provides the
power for voice communication or any other related function to the speakers.
Connection Notes: For the supervised fire system voice coil, parallel input leads are provided on
Series ULD speakers for proper utilization of the electrical supervision scheme. Connect one pair
(red and black) to the incoming line from the fire alert signal source or previous speaker.
Connect the other pair (red and black) to the outgoing line to the next speaker or end-of-line
termination device. A red jumper is connected to the 70.7V 0.5W tap when shipped from the
factory. If desired, move the red jumper to a different transformer power tap lug. See "Figure 1" on
this page for available transformer power taps.
Connection Notes: For the voice/music non-supervised voice coil, connect leads (white and black)
to the incoming line from the signal source or previous speaker. A red jumper is connected to the
70.7V 0.5W tap when shipped from the factory. If desired, move the red jumper to a different
transformer power tap lug. See "Figure 1" this page for available transformer power taps.
Frequency Response: 100Hz - 12kHz + 20dB
2kHz Dispersion at -6dB down points: With SG8 Grille:100 Degrees With WB8 Grille:100 Degrees
Directional Characteristics Test With Full Power Pink Noise Input Measured at 3m:
On Axis = 91.1dBA, -3dBA at 25
8C10DVC Driver Size: 8"
8C10DVC Driver Power Rating: 15 watts RMS
8C10DVC Driver Construction: Dual Paper Cone, Dual 1" Voice Coils, 20 Ga.Stamped Steel Basket
Supervision Capacitor: 10uF 160V. Maximum Allowable Supervision Voltage: 100 VDC.
ELECTRICAL AND AUDIBLE RATINGS
MAXIMUM
TLM572 (#13456)
VOLTAGE
TRANSFORMER TAP
5.0 W.
2.0 W.
70.7 V
1.0 W.
RMS
0.5 W.
0.25 W.
5.0 W.
2.0 W.
25 V
1.0 W.
RMS
0.5 W.
0.25 W.
Note: The UL dBA ratings given above are the low readings from 11 samples so they m ay not be as expected for one sample .
XCP84S ENCLOSURE
ELECTRICAL SPECIFICATIONS
Intended Use: Indoor Dry Locations
o
o
off axis, -6dBA at 55
degrees off axis, 84.1dBA at 90
8C10DVC Impedance: 8 Ohms
8C10DVC Magnet: 10 oz. Ceramic
ULDWB82T572
UL dBA RATING AT 10FT.
88.8
85.2
82.4
79.6
76.4
88.5
85.1
82.3
79.5
76.2
CP84 ENCLOSURE
8641 South Warhawk Road, Conifer Colorado 80433
Tel: 303-670-1099 * FAX: 303-679-8949 /// email: [email protected]
INSTALLATION SHEET #IS-ULD
ULD Series 8" Speaker Assemblies for
Fire Protective Signaling
o
off axis
ULDSG82T572
UL dBA RATING AT 10FT.
88.8
85.2
82.4
79.6
76.4
88.5
85.1
82.3
79.5
76.2
ULP68X ENCLOSURE
www.AVLELEC.com
SIGNALING
U L
R
LISTED
ULDWB82T572
ASSEMBLY
ULDSG82T572
ASSEMBLY
FIGURE 1
#13456
TRANSFORMER TAPS
70V-5W
70V-2W
25V-0.25W
70V-1W
FRONT VIEW
25V-0.5W
70/25V COM
8 OHM
SPKR COM
REAR VIEW
CB84SG ENCLOSURE
FIRE ALARM
EQUIPMENT
28LO
25V-5W
25V-2W
25V-1W
70V-0.5W
70V-0.25W
Page 1 of 2