DeZurik PEC 4200 Manual - Página 17
Navegue en línea o descargue pdf Manual para Unidad de control DeZurik PEC 4200. DeZurik PEC 4200 18 páginas. Eccentric valves
Troubleshooting
Symptom
Packing Leaks.
Valve does
not close.
Valve leaks when
closed.
April 2015
3650-7200 PEC Eccentric Valves
Possible Cause
Packing is loose.
Packing is worn.
Object is wedged
between plug and seat.
Actuator closed position is
out of adjustment.
Plug is worn or damaged.
Rubber on plug is torn.
Page 17
Corrective Action
Adjust Packing.
(See Packing Adjustment
section)
Replace Packing.
(See Packing Replacement
section)
Completely open the valve
to flush object from the
valve. If flushing does not
work, remove valve from
the pipeline and remove
object. (See Removing
Valve from Pipeline
section)
Adjust the closed position
stop. See Actuator
Instructions.
Replace plug. See
Disassembly and
Reassembly sections.
DeZURIK
D10019