Reversing the Positioner Action
To change the positioner action from increasing signal to OPEN to increasing signal to CLOSE, or vice
versa, follow the steps below.
Moving parts from accidental operation of power actuator can cause personal injury or
equipment damage. Disconnect and lock out power to the actuator before servicing.
1. Shut off the supply air pressure and the input signal pressure.
2. On double-acting cylinders, disconnect and reverse the two connections to positioner ports C1
and C2. For spring-return cylinders, proceed to step 3.
3. Remove the positioner cover and dial indicator.
4. Loosen the cam locking nut screw and remove the cam locking nut.
5. Turn the cam over and position the cam so the cam roller is about 1/32" from the stop on the
cam. See Figure 4.
6. Tighten the locking screw — allow room for movement of the cam as the cam locking nut is
tightened.
7. Turn on the supply and input pressures and operate the valve.
8. Adjust the zero and span adjustments, if necessary.
D10327
Figure 4 – Cam Positions