Allied Air 4SCU13 Manual de instrucciones de instalación - Página 3
Navegue en línea o descargue pdf Manual de instrucciones de instalación para Aire acondicionado Allied Air 4SCU13. Allied Air 4SCU13 12 páginas. Split system air conditioner
Elevate Unit
Accumulation of water and ice in base pan may cause
equipment damage.
Elevate unit per local climate and code requirements
to provide clearance above estimated snowfall level and
ensure adequate drainage of unit. Use snow stand in
areas where prolonged freezing temperatures are
encountered.
If conditions or local codes require the unit be
attached to pad or mounting frame, tie down bolts should
be used and fastened through knockouts provided in unit
base pan.
Roof Top Installations
Mount on level platform or frame 6 inches above roof
surface. Place unit above a load-bearing wall and isolate
unit and tubing set from structure. Arrange supporting
members to adequately support unit and minimize
transmission of vibration to building. Ensure roof structure
and anchoring method is adequate for location. Consult
local codes governing rooftop applications.
NOTE: Unit must be level to within ± 2° (± 3/8 in./ft) per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping, and service. For
proper airflow, quiet operation and maximum efficiency.
Position so water, snow, or ice from roof or eaves cannot
fall directly on unit.
506957-02
CAUTION
DO LOCATE THE UNIT:
• With proper clearances on sides and top of unit (a
minimum of 12" on the three sides, service side
should be 24" and 48" on top
• On solid, level foundation or pad
• To minimize refrigerant line lengths
DO NOT LOCATE THE UNIT:
• On brick, concrete blocks or unstable surfaces
• Near clothes dryer exhaust vents
• Near sleeping area or near windows
• Under eaves where water, snow or ice can fall
directly on the unit
• With clearance less than 2 ft. from a second uni
• With clearance less than 4 ft. on top of unit
Indoor Coil Piston Selection
The outdoor section must be matched to a factory
approved indoor section. It is mandatory that the installer
ensure that the correct piston or TXV is installed in the
indoor section. If necessary remove the existing piston
and replace it with the correct piston or TXV. See indoor
unit instructions for details of changing the piston or TXV.
Contact your distributor for accessory piston kits.
The correct piston size is shipped with the outdoor
unit, and also listed in the specification sheet. Do not
use the piston that comes with the indoor unit, unless it
matches the one listed on the outdoor unit.
Refrigeration Line Sets
Use only refrigeration grade copper tubes. Split
systems may be installed with up to 50 feet of line set
(no more than 20 feet verticle) without special consider-
ation (see long line set guide lines).
Liquid
Model
Line
18
3/8 or 1/4
24
3/8 or 1/4
30
3/8
36
3/8
41
- -
42
3/8
47
- -
48
3/8
60
3/8
* Fittings should be supplied by the installer.
1. For lines 25 Ft or over, use 3/8"
2. For lines 25 Ft or over, use 3/4"
3. For lines 25 Ft or over, use 7/8"
4. For lines 25 Ft or over, use 1 1/8"
Do not leave the lines open to the atmosphere for any
period of time, moisture, dirt and bugs may contaminate
the lines.
Issue 1326
13 SEER
Suction
Liquid
Line
Line
1
2
5/8
3/8
1
2
5/8
3/8
3/4
3/8
3
3/4
3/8
- -
3/8
3/4
3/8
3
- -
3/8
7/8
3/8
4
7/8
3/8
14 SEER
Suction
Line
3/4
3/4
3/4
7/8
7/8
7/8
7/8
7/8
1 1/8