CP EBDHS-KNX Manual del producto - Página 8

Navegue en línea o descargue pdf Manual del producto para Sensores de seguridad CP EBDHS-KNX. CP EBDHS-KNX 18 páginas. Ceiling pir hs presence detector

General settings
Setting
Sensor walk test LED
Sensor sensitivity
Lux multiplier
Send light level telegrams every
Group Object
Light level output
Switch inputs
The switch inputs parameters are used to define the behaviour when the two volt-free switch inputs are connected. The
inputs can be used to send dimming commands, recall scenes or send simple switch (on/off) telegrams. It should be
noted that these switch inputs can be used as part of logic functions if required.
Setting
Switch input 1 close action
Switch input 1 close scene number
Switch input 1 open action
Switch input 1 open scene number
Switch input 1 touch action
Switch input 1 scene number 'A'
Switch input 1 scene number 'B'
Switch input 1 hold action
Switch input 2 close action
8
Options
Disable
Enable
0 to 9
Floating point
0 – 65535s
Data Type
9.4 DPT_Value_Lux
Options
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
1 – 64
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
1 – 64
Toggle on/off
Toggle scene A/B
Do nothing
1 - 64
1 - 64
Dim up/down
Dim up
Dim down
Do nothing
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
Description
Enable or disable the sensor walk test LED, triggered
when movement is detected. This is useful for
commissioning, (or if the detector is to be used in
bedrooms). Note that the walk test function can also
be turned on and off via infra-red remote control.
Increase or decrease the detector's sensitivity to
movement. 0 is least sensitive, 9 is most sensitive.
The sensitivity can be overridden via infra-red
remote, but will be overwritten when parameters are
updated via ETS.
Value to multiply raw light level readings by to obtain
true lux value. In practice, this will need to be set with
the aid of a light meter in the environment that the
detector is used in, as reflected light and even choice
of furnishings will dramatically affect the readings
obtained.
Defines how often to send light level telegrams. It is
only possible to send cyclically: immediate
transmission would overload the bus.
Description
Simple cyclical output of current brightness in lux.
Description
Defines what type of command should be sent when
switch input 1 is closed.
Scene number to recall when switch input 1 is closed
Defines what type of command should be sent when
switch input 1 is opened.
Scene number to recall when switch input 1 is
opened.
Defines what command is sent when the button
connected to the switch input is touched (i.e. pressed
and released)
Scene number to recall when scene 'A' is selected.
Scene number to recall when scene 'B' is selected.
Defines what command is sent when the button
connected to the switch input is held. This may be
specified in addition to the touch action above
Defines what type of command should be sent when
switch input 2 is closed.