CP Electronics EBDSPIR-AD-IP Manual del producto - Página 9
Navegue en línea o descargue pdf Manual del producto para Sensores de seguridad CP Electronics EBDSPIR-AD-IP. CP Electronics EBDSPIR-AD-IP 13 páginas. Ceiling pir presence detector – 1-10v dimming
Parameter Name
Default Value
Detector Parameters
Walk Test LED
Off
Time Out
20 minutes
(Time adjustment)
Manual Time Out
10 minutes
Sensitivity On
9
Sensitivity Off
9
Lux time
0
Power Up State
On
Disable Detector
N
On Delay
0 minutes
Inhibit
4 seconds
Factory default
-
Channel Modes
Switch only
-
Switch and dim
Default
together
User Modes
Raise
-
Lower
-
Scene up
-
Scene down
-
Scene #
-
Override On
-
Override Off
-
Cancel
-
Range / Options
Description
When set to On this causes a red LED to flash on the sensor when it detects
On or Off
movement. Use this feature to check for adequate sensitivity levels.
0-99 minutes
Once the detector is turned on, this value sets how long the lights will stay on once
movement has ceased. Select 0 for 10 second delay – use for commissioning only.
When a manual operation occurs, either via the switch input or the infrared, it
0-99 minutes
invokes the timeout period.
Example 1: a detector in presence mode has a detector timeout of 15 minutes and
a manual timeout of 3 minutes. When the user leaves the room they press the off
button. The sensor will revert to automatic after 3 minutes, and then walking back
in the room will turn the lights on.
Example 2: using the settings above, the user turns the lights off (say for a
presentation) but stays in the room. Every time a movement is detected, the
manual timeout period is re-triggered, but when it doesn't pick up for the short
timeout period, the sensor will timeout and revert to automatic. This means the
lights may turn on inadvertently during the presentation, if the occupants are still
for the manual timeout period, so adjust the timing carefully.
1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is already on. *UHS5
sets Sensitivity On and Off to the same value.
Sensitivity level for detecting movement when the detector is off. *UHS5 sets
1 (min) to 9 (max)
Sensitivity On and Off to the same value.
0 (disabled)
If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
1-99 minutes
timed delay the lux change reverses then the process is cancelled. Lux Time
enables absence detection to be implemented with a lux off level set. When the
button is pressed, the lights will go on, regardless of ambient light level. However,
if there is sufficient ambient light, they will turn off again after the Lux Time. Note
that whenever the an external switch is pressed, whether in absence or presence
mode, if the lights were out because of the lux level, they will be immediately
turned on again for at least the Lux Time.
On or Off
Select No for a 30 second delay on start up. If Yes is selected, there will be no
delay on start up and the detector will always power up detecting.
Y or N
Disables detection, leaving the relay output permanently off with the dimming
output operational. This mode is used when the unit is for maintained illuminance
only.
0-99 minutes
The On Delay to allows the first channel to switch on after the second channel. A
typical application for this would be where a detector is controlling lighting and air
conditioning in an area. When the occupant is detected, the lighting will be turned
on immediately, whereas the air conditioning may be turned on after 15 minutes. If
the area is vacated and the detector times out before the delay, then the air
conditioning would never go on. The delay can be set only for channel 1 using the
on delay parameter.
1 to 999 seconds
When the detector turns off, a delay is instigated to prevent retriggering. In certain
circumstances this delay may not be enough. This parameter allows the delay to
be changed.
-
Restores factory default settings
-
Usually used for absence detection - in this mode the dimming channel is not used.
The detector will switch and dim the lighting together.
-
Increase light level. Reverts when occupancy cycle complete.
-
Decrease light level. Reverts when occupancy cycle complete.
-
-
Steps up between 6 pre-defined scenes.
-
Steps down between 6 pre-defined scenes.
Select the individual scene, between 0 and 6.
-
(1 = min. output; 2 = 10%; 3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%)
-
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period .
If the lights are on, sending the IR command will turn them off immediately. After
-
the manual timeout period (described above), the sensor will revert to automatic.
-
Cancels the on or off override, returning the detector to normal operation.
Advanced programming
UHS5 UNLCDHS
*
*
9