CP Electronics EBDSPIR-HB-AD Manual del producto - Página 6

Navegue en línea o descargue pdf Manual del producto para Sensores de seguridad CP Electronics EBDSPIR-HB-AD. CP Electronics EBDSPIR-HB-AD 12 páginas. High bay analogue dimming pir presence detector

4. Programming

All the following functions can be programmed using the remote control DD-LCDHS-LR handset:
1.
Detector Parameters (factory default in brackets):
1.1 Time adjustment
1.2 Sensitivity On (9)
1.3 Sensitivity Off (9)
1.4 Power Up On (Y)
1.5 Walk Test (N)
1.6 Disable Detector (N)
1.7 Factory Default
2.
Modes (factory default in brackets):
2.1 Channel Modes
2.1.1 Switch only
2.1.2 Switch and dim together (default)
2.1.3 Switch and dim separate
2.2 Switch Modes
2.2.2 2 position switch separate
2.2.3 1 position switch together
2.2.4 1 position switch separate
3.
Switching Channel 1 functions (factory default in brackets):
3.1 Presence detection
3.2 Absence detection
3.3 Switch level on (9)
3.4 Switch level off (9)
page 6
10 seconds to 99 minutes time delay (select 0 for 10 second
delay – use for commissioning only).
Sensitivity level when the detector is already operational
adjustable between 1 (min.) and 9 (max.)
Sensitivity level for switching the detector on – adjustable
between 1 (min.) and 9 (max.).
Select No for a 30 second delay on start up. If Yes is selected,
there will be no delay on start up and the detector will always
power up detecting.
An LED behind the detector lens will flash to show movement
has been detected (use for commissioning).
Disables detection, leaving the relay output permanently off
with the dimming output operational. This mode is used when
the unit is for maintained illuminance only.
Restores factory default settings.
Usually used for absence detection - in this mode the dimming
channel is not used.
The detector will switch and dim the lighting together.
Not used
A single centre biased retractive switch will be used to
control dimming and switching.
A single centre biased retractive switch will be used to
control dimming and switching.
Not used.
Auto switch on with detection, auto off after movement ceases
and time delay ends.
Manual switch on, auto off after movement ceases and time
delay ends.
Lux level setting to prevent the luminaires being switched on if
the ambient light level is sufficient (adjustable between 1
and 9). The luminaires will always be switched on at level 9.
For a higher resolution of ‗switch level on' a scale of 101-199
is available in the ‗Special menu'.
Lux level setting to switch the luminaires off during occupancy
if the ambient light level goes above the setting (adjustable
between 1 and 9). Level 9 will always keep the lights on. This
setting can be used for ―window row switching‖.
For a higher resolution of ‗switch level off' a scale of 101-199
is available in the ‗Special menu'.