Dell P570 Manual del usuario - Página 28
Navegue en línea o descargue pdf Manual del usuario para Servidor Dell P570. Dell P570 37 páginas.
También para Dell P570: Manual del usuario (35 páginas), Manual del usuario (35 páginas)
Table 34. Expanded operating temperature specifications (continued)
Expanded operating temperature
≤ 1% of annual operating hours
NOTE:
When operating in the expanded temperature range, appliance performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported in the System
Event Log.
Expanded operating temperature restrictions
● Do not perform a cold startup below 5°C.
● The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
● 150 W/8 core, 165 W/12 core and higher wattage processor [Thermal Design Power (TDP)>165 W] are not supported.
● Redundant power supply units are required.
● Non-Dell EMC qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
● Mid drive tray is not supported.
● Rear storage devices or drives are not supported.
● GPU is not supported.
Thermal restrictions
Following table lists the configuration required for efficient cooling.
Table 35. Thermal restrictions configuration
Supported
Number
VxRail
of proc
Config
VxRail P
1
Series
appliance
VxRail P
2
Series
appliance
VxRail S
1
Series
appliance
VxRail S
2
Series
appliance
28
Technical specifications
Heatsink
One 1U standard heat sink
for CPU ≤ 125 W
One 2U standard heat sink
for CPU > 125 W
Two 1U standard heat sink
for CPU ≤ 125 W
Two 2U standard heat sink
for CPU > 125 W
One 1U high performance
heat sink
Two 1U high performance
heat sink
Specifications
For temperatures between 35°C to 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the appliance can operate down to –5°C or up to 45°C
for a maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228
ft).
Processor/DIMM
blank
Required
Not required
Required
Not required
DIMM
Type of air
blanks
shroud
Not
Standard
required
Not
Standard
required
Required
Not required
Required
Not required
Fan
Four standard
fans and one
blank to cover
two fan slots
Six standard
fans
Six high
performance
fans
Six high
performance
fans