Dell PowerEdge 6x00 Series Instalación de bastidores - Página 22

Navegue en línea o descargue pdf Instalación de bastidores para Servidor Dell PowerEdge 6x00 Series. Dell PowerEdge 6x00 Series 34 páginas. Rack installation guide
También para Dell PowerEdge 6x00 Series: Instalación de bastidores (37 páginas), Manual de instalación (37 páginas)

Dell PowerEdge 6x00 Series Instalación de bastidores
(Rev. 9/8/00) FILE LOCATION: S:\SYSTEMS\MARCONI\Rackingd\7U\05KCEa00\05KCEeb0.fm
8
Rack Installation Guide

Installing the Slide Assemblies in the Rack

You must allow 7 U (12.25 inches) of vertical space for each PowerEdge system you
install in the rack.
The rails of the rack are marked by small indentations in 1-U increments (see
Figure 6).
1 U (1.75 inches)

Figure 6. One Rack Unit

For more information, see the Dell Rack Advisor software available on the Dell World
Wide Web site at http://support.dell.com.
WARNING: If you are installing more than one computer, install the slide
assemblies so that the first computer is installed in the lowest available
position in the rack.
To determine where to install the slide assemblies in the rack, perform the following
steps:
1.
Place the front of the template over the front rack rails (see Figure 7).
The printing on the template identifies the side facing outward as the template
front.
2.
Position the bottom of the template where the system's lower edge will be
located.
DELL CONFIDENTIAL - Preliminary
9/8/00