Access Modification and Fire Brick Installation
Through-Wall Accesses:
Gas Line Feed: The provision for installation of a gas pipe
is only for connection to a decorative gas appliance or a gas
log lighter. The decorative gas appliance must comply with
Outdoor for Decorative Gas Appliances for installation
in Vented Fireplaces, ANSI Z21.60. The decorative gas
appliance should be installed in accordance with the National
Fuel Gas Code, ANSI Z223.1.
Important: Gas line for gas log sets used in the Isokern
firebox can be routed through the side wall, back wall or floor
of the firebox by drilling an appropriately sized hole using a
masonry drill bit.
Be sure to follow the gas log Appliance
Manufacturer's explicit electrical line connection instructions
for vented masonry fireplace installations.
Note: Gas Line and Electric Line must be fed through separate
access holes.
CAUTION: All access holes must be grouted with mortar to
seal any gaps or cracks.
Fire Brick Installation:
The manufacturer requires that the firebox be lined
with a minimum one and one-eighth (1-1/8") thick rated fire
brick. The pattern for the fire brick lining is an owner option.
Standard N or S -Type brick mortar is a suitable fire brick
mortar. Add a small portion of Earthcore mortar to make it a
sticky consistency with a 1/4" notch trowel bed joint. Because
of different climates, the use of good masonry practices for
your area should also be considered.
Hint: Before application, wet down the surface area, then
apply water dipped firebrick for improved adherence.
All required through-wall accesses (gas and electrical
line feeds and combustion air supply access holes) should be
drilled before the required fire brick lining is installed.
It takes a total of about five gallons of mortar mix
(dry measure) to fire brick line a firebox. (60 & 72 will require
more mortar)
Face joints of one quarter inch (1/4") to three-eighths
inch (3/8") give a good appearance to the finished brick-work
however, larger face joint dimensions are also acceptable.
Step 1. Wet mop the inside of the firebox with a damp sponge
to remove dust and loose particles from the interior before
installing fire brick.
Step 2. Start the fire brick at the front edge of the floor of the
Isokern firebox, proceeding inward toward the back.
Step 3. Next, apply fire brick to the back wall of the unit
starting at the bottom of the back wall and working upward to
the top of the back wall.
Step 4. Finally, set the side wall fire brick by starting at the
front edge of the unit's side wall and working inward toward
the back wall fire brick.
Earthcore makes no claims as to the performance
of fire brick or fire brick mortars.
Typical placement of
gas or electric line
(see detail below)
Fire Brick
Floor
(Built First)
NOTE:
The 60 & 72 Models
Require Minimum 4" Fire Brick
on the Side Walls, 1 1/8"
Minimum Fire Brick on the
Floor and Back Wall.
6
Firebrick
side
Gas or Electric
line
NOTE: Fill any gaps around
line with Earthcore Mortar
1/2" Expansion
Gap
Fire Brick Floor
(Built First)
1/2" Expansion
Gap