Dell S4100-ON Series Manual de instalación - Página 18

Navegue en línea o descargue pdf Manual de instalación para Interruptor Dell S4100-ON Series. Dell S4100-ON Series 48 páginas.
También para Dell S4100-ON Series: Manual de instalación (47 páginas), Manual de instalación (21 páginas), Manual de instalación (49 páginas)

Dell S4100-ON Series Manual de instalación

Cabinet placement

Install the S4100–ON Series (S4128F-ON, S4148F-ON, and S4148FE-ON) only in indoor cabinets designed for use in a controlled
environment.
Do not install the switch in outside cabinets. For cabinet placement requirements, see
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA) standard.
Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.

Rack mounting

When you prepare your equipment rack, ensure that the rack is grounded. Ground the equipment rack to the same ground point the power
service in your area uses. The ground path must be permanent.

Switch ground

Dell EMC recommends grounding your switch. Use the S4100–ON Series switch in a CBN.
NOTE:
For AC-powered switches, although the third conductor of the AC power cord provides a ground path, Dell EMC
recommends grounding your switch with a dedicated ground wire.
NOTE:
For DC-powered switches, the only way to safely ground your switch is to attach a dedicated ground wire.

Fans and airflow

The fans on the S4100–ON Series (S4128F-ON, S4148F-ON, and S4148FE-ON) support two airflow options: normal and reverse.

Fan combinations

Fan installation is done as part of the factory install based on SKU type. The S4100–ON Series has stock keeping units (SKUs) that support
the following configurations:
AC PSU with fan airflow from the I/O to the PSU—normal
AC PSU with fan airflow from the PSU to the I/O—reverse
DC fan unit with airflow from the I/O to the PSU—normal
DC fan unit with airflow from the PSU to the I/O—reverse
Be sure to order the fans suitable to support your site's ventilation. Use a single type of airflow fan in your switch. Do not mix reverse and
normal airflows in a single switch.
For proper ventilation, position the S4100–ON Series switch in an equipment rack or cabinet with a minimum of 5 inches (12.7 cm) of
clearance around the exhaust vents. The fan speed varies based on internal temperature monitoring. The switch never intentionally turns
off the fans.
For more information, see Fans.

Power

Connect the switch to the applicable power source using the appropriate power cable. An AC power cable is included with each PSU.
When installing AC or DC switches, follow the requirements of the National Electrical Code ANSI/NFPA 70, where applicable.
The switch is powered-up when the power cable is connected between the switch and the power source.
18
Site preparations
Site
selection.