Dell S4128F-ON Series Manual de instalación - Página 23
Navegue en línea o descargue pdf Manual de instalación para Interruptor Dell S4128F-ON Series. Dell S4128F-ON Series 48 páginas.
También para Dell S4128F-ON Series: Manual de instalación (47 páginas)
Figure 11. 1U tool-less installation
2
Align and seat the front flange pegs in the holes on the front side of the vertical post.
NOTE:
Be sure that the rails click into place and are secure.
3
Repeat this procedure for the second rail.
4
To remove each rail, pull on the latch release button on each flange ear and unseat each rail.
Two-post flush-mount installation
NOTE:
For more installation instructions, see the installation labels attached to the rail assembly.
1
For this configuration, remove the latch castings from the front side of each ReadyRails assembly, item 1.
To remove the two screws from each front flange ear on the switch side of the rail and remove each latch casting, use a Torx
screwdriver. Retain the latch castings for future rack requirements. It is not necessary to remove the back flange castings.
S4100–ON Series installation
23