6.6. Functioning of the shared channel M1 + M2
A transmitter memorized on the shared channel has the following working:
If DIP 1 and 3 set in the same way: functioning set by the DIP
If DIP 1 and 3 set in different way: functioning set by the DIP to OFF (see 4.1)
A command received by a transmitter memorized on the shared channel synchronizes the movement.
Example: awning 1 opening, awning 2 closing: the first command received stops the automations,with a second command the automations move in the
same direction.
7. Clock function
The clock function cannot be used with the dead man modality
The clock function is used in those situations where you want to open and close the automation at specific times.
An external timer is necessary with a dry contact which remains closed for all the time where the automation must remain open, and must open the
contact when the automation must close. The contact must be connected to the input "open" of the respective motor, after 4 minutes of closed contact
the control unit enters the "Clock function". The wall buttons can be normally used if the "Clock" function is not active, on the contrary any command,
also by transmitter is ignored. As usual, a wind alarm closes the automation which will completely reopens itself as soon as this is finished,
independently from the position of the dips of automatic reopening (dip 2 and 4).
8. Limit switch and working time adjusting
The position of limit switch in opening of the automation is settable by the limit switches of the used motors. However the control unit is provided with a
maximum working time of 7 minutes, to allow the automatic stop of the motor also in case of failure of the limit switches of the motor.
9. Expansion of the wind sensor
JUMPER CLOSED
Setting of the jumper for expansion wind sensor
With a wind sensor used with one control
unit, leave the expansion jumper of the wind
sensor closed.
CT1
CT1
CT2
CT3
CT4
Power voltage
Motor output
Card absorption
Motor operation time
Standby time after wind alarm
Operating temperature
Frequency (*)
Radio range in open field (*)
Type of antenna (*)
Number of available codes (*)
Memorisable channels (*)
(*) technical features valid only in presence of a radio receiver
GUARANTEE - In compliance with legislation, the manufacturer's guarantee is valid from the date stamped on the product and is restricted to the re-
pair or free replacement of the parts accepted by the manufacturer as being defective due to poor quality materials or manufacturing defects. The
guarantee does not cover damage or defects caused by external agents, faulty maintenance, overloading, natural wear and tear, choice of incorrect
product, assembly errors, or any other cause not imputable to the manufacturer. Products that have been misused will not be guaranteed or repaired.
Printed specifications are only indicative. The manufacturer does not accept any responsibility for range reductions or malfunctions caused by environ-
mental interference. The manufacturer's responsibility for damage caused to persons resulting from accidents of any nature caused by our defective
products, are only those responsibilities that come under Italian law.
6-1622294
rev 2
04/05/2015
JUMPER OPEN
CT1
With a wind sensor used with SIX control units, leave closed
the expansion jumper of the wind sensor of the first control
unit and remove the one present in the second and in the
third, fourth, fifth and sixth control unit.
CT5
CT6
Technical specifications B2VR PROX
230 Vac +10% -15%
2 x 230Vac 500W MAX cosΦ > 0.8
3W MAX (excluding accessories and utilities)
7 minutes
7 minutes
-10°C ... +60°C
433.92 MHz Super-reactive band
20 – 40m
Incorporated stylus
18 billion billion (reception BIROLÆ VARIABLE CODE AND CLARUS)
1000 with B.RO 1000 memory module (VARIABLE CODE)
ITA
ENG
JUMPER OPEN
With a wind sensor used with THREE control units, leave
closed the expansion jumper of the wind sensor of the first
control unit and remove the one present in the second and
in the third control unit.
CT2
CT3
433.92 MHzSuper-reactive band
30 – 60m
FRA
ESP
DEU
POR
(DIP 1 and 3 OFF)
JUMPER OPEN
CT= CONTROL UNIT
40.665 MHz Quartzed