Miele DA 219-2 Instrucciones de uso e instalación - Página 7

Navegue en línea o descargue pdf Instrucciones de uso e instalación para Campana de ventilación Miele DA 219-2. Miele DA 219-2 44 páginas. Ventilation system
También para Miele DA 219-2: Instrucciones de uso e instalación (40 páginas)

Miele DA 219-2 Instrucciones de uso e instalación
Installation
, WARNING
To reduce the risk of fire only
use metal ductwork.
When installing the hood, follow the
recommended minimum safety
distances between a Miele cooktop and
the hood:
– 22" (55 cm) above electric cooktops,
– 26" (65 cm) above gas cooktops,
– 26" (65 cm) above an open grill.
If local building codes require a greater
safety distance, follow their
requirement.
For non-Miele cooking appliances
maintain the safety distances
recommended by the appliance
manufacturer in their instructions.
If there is more than one appliance
beneath the hood and they have
different minimum safety distances
always select the greater distance.
Be careful not to damage hidden
electrical wiring or plumbing when
cutting or drilling into the wall or ceiling.
Do not use an extension cord to
connect the appliance to electricity.
Extension cords do not guarantee the
required safety of the appliance, (e.g.
danger of overheating).
Do not install this hood over
cooktops burning solid fuel.
IMPORTANT SAFETY INSTRUCTIONS
be made of approved non-flammable
materials.
flue, or room ventilating ductwork. Seek
professional advice before connecting
an exhaust hood vent to an existing,
inactive chimney or vent flue.
and exhausting of all non-electric
heating appliances (water heaters, gas
cooktops, gas ovens, etc.), otherwise
backdrafts may occur. Follow the
heating manufacturer's guidelines and
safety standards or those published by
the National Fire Protection Association
(NFPA), or the American Society for
Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE).
If in doubt, consult an experienced
professional.
Any fittings, sealant, or materials
used to install the ductwork must
Never connect an exhaust hood to
an active chimney, dryer vent, vent
Ducted fans must always be
vented outdoors.
Make sure that the airflow in the
room is sufficient for combustion
7