ABB CPS6000 Manual de inicio rápido - Página 3
Navegue en línea o descargue pdf Manual de inicio rápido para Equipamiento industrial ABB CPS6000. ABB CPS6000 8 páginas.
También para ABB CPS6000: Manual de inicio rápido (6 páginas)
Step # 3 – Connect DC Output to Loads and Batteries
The figure (right) shows the DC circuit description for the
distribution system. The system is equipped with 20 (19" panel) or
26 (23" panel) bullet-style distribution positions. Each of the
positions in the distribution panel are selectable between either
battery inputs or load outputs.
Breaker sizes up to 250A, TPS fuses to 70A and GMT fuses to 12A are
available. DC Connections are made with double hole lugs on ¼-20
studs on 5/8" centers. The maximum tongue width for breaker
connections is 0.68".
Load and battery cabling, showing multi-pole adapters
installed in distribution space
The correct multi-pole adapters must be used with multi-
pole breakers
Ordering code
2 - pole Adapter bus for 100-150A breakers; used for 3/8" on 1" lugs (order 2 per 3pole breaker to
850021775
accommodate load and return lugs.)
3 - pole Adapter bus for 200-250A breakers; Centered connection (order 2 per 3 pole breaker to
850021955
accommodate load and return lugs.)
Page 3
© 2023 ABB. All rights reserved.
Description
CPS6000_Series II External Distribution_QSG
Picture
Version 2.0