Burkert 8644 AirLINE Manual de inicio rápido - Página 10
Navegue en línea o descargue pdf Manual de inicio rápido para Sistemas de control Burkert 8644 AirLINE. Burkert 8644 AirLINE 17 páginas.
→
Fasten the standard rail firmly in the control cabinet.
→
Establish a short, wide PE connection between the standard rail
and the control cabinet.
The valve terminal must be freely accessible from above.
Ensure good heat dissipation!
Recommended distance when installing in a control cabinet:
A
30 mm
B
30 mm
6.2.2. Installation of AirLINE Quick
To install AirLINE Quick, a notch must be first of all provided on the
base or the wall of the control cabinet, e.g. through lasing or punching.
For the dimensions of the relevant flange image, refer to chapter
"Tab. 1: Dimensions of the flange images for AirLINE Quick".
The distances to the left, right, front and top depend on the selected
valve terminal configuration.
Recommended distance in the control cabinet to the valve
terminal:
left
right
30 mm
60 mm
HINWEIS!
The opening on the control cabinet must be burr-free to
prevent damage to the seal of the AirLINE Quick adapter.
→
Without damaging the seal of the AirLINE Quick adapter, insert it
into the groove of the flange opening.
10
C
30 mm
D
60 mm
front
top
30 mm
50 mm
english
Type 8644
Assembly
→
Position the valve terminal in the control cabinet on the prepared
opening.
→
From outside attach the stability plate to prevent distortion and
secure with screws M 5 x 10 from the enclosed fastening set.
Fig. 5:
Placing the valve terminal in the control cabinet
Fig. 6:
Attaching the stability plate
Valve terminal
Type 8644
AirLINE Quick
adapter
Control cabinet
Screws M 5 x 10
Stability plate