Aquarii Zino Manual de instalación - Página 10
Navegue en línea o descargue pdf Manual de instalación para Luz de inundación Aquarii Zino. Aquarii Zino 11 páginas. Slope recessed
Secure 0-10V Connection
See the 0-10V Wiring Diagram for a Zino LED Fixture below:
NOTE:
All 0-10V Analog Wiring should be run as Class 2 per National Electric Code (NEC) Article 725. See the 0-10V Information
section of this manual for more information.
Follow the steps below to secure the sites 0-10V Communication Wiring to the fixture.
1. Ensure the local sites power supply is shut-off for personal safety.
2. Determine the type of circuit present at the local site.
3. Secure the Screw Terminal Plug-in Connection from the local site to the 0-10V Communication Board.
4. Confirm the Polarity for 0-10V Communication Wiring.
5. Test the fixture to ensure proper function.
8