Fig 2. Typical installation example for Level Switch LSM-P3.

1.3.3 ELECTRICAL

1.3.3.1
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 &
0.4
1.3.3.2
All wiring must comply with the latest edition of local wiring regulations.
1.3.3.3
Wear anti-static wrist strap at all times to avoid static discharge causing problems with the
built in electronic program.
1.3.3.4
Connect incoming electrical mains supply to identified terminals in control box (see fig. 3).
Ensure voltages and frequency indicated on the labels correspond with supply mains data and
that the supply fuse ratings are correct for the total current rating of the equipment.
1.3.3.5
Connect volt free relay terminals as required. (see fig 3).
Aquatech-Pressmain Limited Instruction manual\Liquid Level Switch LSM
Level Switch LSM