Alpha IP FAL 41011-10 Manual - Página 13
Navegue en línea o descargue pdf Manual para Accesorios Alpha IP FAL 41011-10. Alpha IP FAL 41011-10 17 páginas.
The configuration menu for the Alpha IP base station includes device parameters "UnP1/UnP2" and
channel parameters "ChAn", allowing to change lead and follow-up times for the pump, setback temper-
atures, time intervals and many other parameters. The following table shows the available parameters:
UnP1:
Parameters
Antifreeze temperature
Pump control
Load equilibration:
Heating zones will be con-
trolled in a staggered way if
possible
Load collection:
Heating
zones
controlled collectively.
Actuator
NC - Normally Closed
NO - Normally Open
*If heating zone 1 is used as
pump control, it is necessary to
teach in a wall thermostat to
this heating zone, if an adap-
tation of the pump parameters
shall be performed.
Emergency operation
in heating mode
Emergency operation
in heating mode
Index
Value
P024
3
4
5
...
16 (default)
...
19
20
P025
0
1
2
are
3
types:
4 (default)
5
6
7
P026
0
1
...
25 (default)
...
99
100
P032
0 (default)
1
...
99
100
Meaning
Antifreeze protection inactive
2.0 °C
2.5 °C
...
8.0 °C
...
9.5 °C
10.0 °C
active,
with
load
actuator type NC
active, with load equilibration
actuator type NO
active, with load collection
actuator type NC
active, with load collection
actuator type NO
inactive, with load equilibration
actuator type NC
inactive, with load equilibration
actuator type NO
inactive, with load collection
actuator type NC
inactive, with load collection
actuator type NO
0 %
1 %
...
25 %
...
99 %
100 %
0 %
1 %
...
99 %
100 %
Configuration
equilibration,
13