También para ABB ACS355 series: Manual complementario (20 páginas), Manual de instalación rápida y puesta en marcha (2 páginas), Manual complementario (16 páginas), Manual de instalación rápida y puesta en marcha (2 páginas), Instrucciones de instalación (4 páginas), Instrucciones de instalación (4 páginas)

ABB ACS355 series Manual de instalación rápida y puesta en marcha
ENTRY OF START-UP DATA (parameter group 99)
If you have an assistant control panel, select the
9901
language. See parameter
for the values of
the available language alternatives.
Select the motor type (
9903
).
1 (
AM
): Asynchronous motor
2 (
PMSM
): Permanent magnet synchronous
motor.
9903
Setting of parameter
is shown below as an
example of parameter setting with the basic
control panel.
1. To go to the Main menu, press
if the
bottom line shows OUTPUT; otherwise press
repeatedly until you see MENU at the
bottom.
2. Press keys
/
until you see "PAr".
3. Press
. Panel changes to Parameter
mode.The display shows the number of one of
the parameter groups.
4.Find the appropriate parameter group (
99
)
with keys
/
.
5. Press
. The display shows one of the
parameters in the selected group. Find the
appropriate parameter (
9903
) with keys
/
.
6. Press and hold
for about two seconds
until parameter value is shown with
SET
under
the value. If necessary, change the value with
keys
/
.
7. Save the parameter value by pressing
.
Select the application macro (
9902
) according
to how the control cables are connected.
The default value 1 (
ABB STANDARD
) is suitable
in most cases.
9904
Select the motor control mode (
).
VECTOR: SPEED
1 (
) suits most cases
2 (
VECTOR: TORQ
) suits torque control
3 (
SCALAR: FREQ
) suits if control accuracy is not
important, and for certain special cases. See
user's manual. Not for permanent magnet
synchronous motors.
Enter the motor data from the motor
nameplate: motor nominal voltage (
9905
),
nominal motor current (
9906
), motor nominal
frequency (
9907
), motor nominal speed (
9908
),
motor nominal power (
9909
)
Select the motor identification method (
9910
).
The default value 0 (
OFF/IDMAGN
) using the
identification magnetization is suitable for
most applications. It is applied here. (Requires
also that
9904
is set to 1 (
VECTOR: SPEED
) or
2 (
VECTOR: TORQ
)).
IDENTIFICATION MAGNETIZATION WITH ID RUN SELECTION 0 (
LOC
Press key
to switch to local control (LOC
REM
shown on the left).
Press
to start the drive. The motor model
is now calculated by magnetizing the motor for
10 to 15 s at zero speed.
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
1. If the drive is in remote control (REM shown
on the left), switch to local control by pressing
LOC
.
REM
2. To go to the Main menu, press
if the
bottom line shows OUTPUT; otherwise press
repeatedly until you see MENU at the
bottom.
3. Press keys
/
until you see "rEF"
and press
.
4.Increase the frequency reference from zero to
a small value with key
.
5. Press
to start the motor.
6. Check that the actual direction of the motor is
the same as indicated on the display (FWD
means forward and REV reverse).
7. Press
to stop the motor.
To change the forward and reverse rotation
directions (with a parameter):
Invert the phases by changing the value of
parameter
9914
to the opposite, ie, from 0 (
NO
)
YES
to 1 (
), or vice versa.
Verify your work by repeating the rotation
direction check as described above.
SPEED LIMITS AND ACCELERATION/DECELERATION TIMES
Set the minimum speed (
2001
), maximum speed
(
2002
), acceleration time 1 (
2202
), and
deceleration time 1 (
2203
)
SAVING A USER MACRO AND FINAL CHECK
The start-up is now completed. If you want to
save your setting as a user macro, scroll to
Parameter 9902 and select value USER S1 SAVE.
Check that there are no faults or alarms shown
on the display.
The drive is now ready for use.
Configure fieldbus communication (optional)
See the drive user's manual.
Related documents
ACS355 user's manual
ACS355 manual list
3AUA0000066143
9AKK107680A5563
3AXD50000622467 Rev A EN 2020-04-21
© Copyright 2020 ABB. All rights reserved.
Fault codes
This is a short list of fault messages.
REM
PAR EDIT
Fault
Description
9901 LANGUAGE
ENGLISH
0001
OVERCURRENT - Output current has exceeded trip level.
0002
DC OVERVOLT - Excessive intermediate circuit DC voltage.
[0]
00:00
CANCEL
SAVE
0003
DEV OVERTEMP - Drive IGBT temperature is excessive.
0004
SHORT CIRC - Short-circuit in motor cable(s) or motor.
9903
REM
0006
DC UNDERVOLT - Intermediate circuit DC voltage is not sufficient.
PAR
FWD
0009
MOT OVERTEMP - Motor temperature estimation is too high.
0016
EARTH FAULT - Drive has detected earth (ground) fault in motor or motor cable.
0022
SUPPLY PHASE - Intermediate circuit DC voltage is oscillating due to missing
input power line phase or blown fuse.
rEF
0044
SAFE TORQUE OFF - STO (Safe torque off) requested via STO terminal and it
REM
functions correctly. Parameter 3025 STO OPERATION is set to react with fault.
MENU
FWD
Ratings
PAr
ACS355-...
REM
MENU
FWD
x = E/U
-01-
REM
PAR
FWD
1-phase
U
= 230 V (200...240 V)
N
-99-
01x-02A4-2
REM
01x-04A7-2
PAR
FWD
01x-06A7-2
01x-07A5-2
9903
REM
01x-09A8-2
U
3-phase
= 230 V (200...240 V)
PAR
FWD
N
03x-02A4-2
01
03x-03A5-2
REM
03x-04A7-2
PAR
SET
FWD
03x-06A7-2
03x-07A5-2
9903
REM
03x-09A8-2
PAR
FWD
03x-13A3-2
03x-17A6-2
9902
03x-24A4-2
REM
03x-31A0-2
PAR
FWD
03x-46A2-2
9904
3-phase
U
= 400/480 V (380...480 V)
N
REM
03x-01A2-4
PAR
FWD
03x-01A9-4
03x-02A4-4
03x-03A3-4
...
03x-04A1-4
03x-05A6-4
03x-07A3-4
03x-08A8-4
03x-12A5-4
9910
REM
03x-15A6-4
PAR
FWD
03x-23A1-4
03x-31A0-4
03x-38A0-4
OFF/IDMAGN
)
03x-44A0-4
LOC
9910
I
continuous rms input current (for dimensioning cables and fuses)
PAR
FWD
1N
I
(480 V) continuous rms input current (for dimensioning cables and fuses) for drives with
1N
480 V input voltage
I
continuous rms current. 50% overload is allowed for one minute every ten
2N
minutes.
I
maximum (50% overload) current allowed for one minute every ten minutes
2,1/10
I
maximum output current. Available for two seconds at start, otherwise as long
LOC
9910
2max
as allowed by the drive temperature.
P
typical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The
N
PAR
FWD
horsepower ratings apply to most NEMA 4-pole motors.
LOC
PAr
Fuses and typical power cable sizes
MENU
FWD
The table list the fuses for protection against short-circuits in the input power
cable or drive. The table also shows typical power cable sizes.
xxx
LOC
.
ACS355-...
Hz
SET
FWD
x = E/U
forward
reverse
1-phase
U
= 230 V (200...240 V)
N
01x-02A4-2
01x-04A7-2
01x-06A7-2
LOC
9914
01x-07A5-2
01x-09A8-2
PAR
FWD
3-phase
U
= 230 V (200...240 V)
N
03x-02A4-2
03x-03A5-2
LOC
2001
03x-04A7-2
03x-06A7-2
PAR
FWD
03x-07A5-2
03x-09A8-2
LOC
9902
03x-13A3-2
03x-17A6-2
PAR
FWD
03x-24A4-2
03x-31A0-2
03x-46A2-2
U
3-phase
= 400/480 V (380...480 V)
N
03x-01A2-4
03x-01A9-4
03x-02A4-4
03x-03A3-4
03x-04A1-4
03x-05A6-4
03x-07A3-4
03x-08A8-4
03x-12A5-4
03x-15A6-4
03x-23A1-4
03x-31A0-4
03x-38A0-4
03x-44A0-4
1)
If 50% overload capacity is needed, use the larger fuse alternative.
Ambient conditions
Requirement
Installation altitude
Surrounding air
temperature
Relative humidity
Input
Input with
Output
choke
I
I
I
I
I
I
I
1N
1N
1N
1N
2N
2,1/10
2max
(480 V)
(480 V)
A
A
A
A
A
A
A
kW
6.1
-
4.5
-
2.4
3.6
4.2
0.37
11
-
8.1
-
4.7
7.1
8.2
0.75
16
-
11
-
6.7
10.1
11.7
1.1
17
-
12
-
7.5
11.3
13.1
1.5
21
-
15
-
9.8
14.7
17.2
2.2
4.3
-
2.2
-
2.4
3.6
4.2
0.37
6.1
-
3.5
-
3.5
5.3
6.1
0.55
7.6
-
4.2
-
4.7
7.1
8.2
0.75
12
-
6.1
-
6.7
10.1
11.7
1.1
12
-
6.9
-
7.5
11.3
13.1
1.5
14
-
9.2
-
9.8
14.7
17.2
2.2
22
-
13
-
13.3
20.0
23.3
3
25
-
14
-
17.6
26.4
30.8
4
41
-
21
-
24.4
36.6
42.7
5.5
50
-
26
-
31
46.5
54.3
7.5
69
-
41
-
46.2
69.3
80.9
11.0
2.2
1.8
1.1
0.9
1.2
1.8
2.1
0.37
3.6
3.0
1.8
1.5
1.9
2.9
3.3
0.55
4.1
3.4
2.3
1.9
2.4
3.6
4.2
0.75
6.0
5.0
3.1
2.6
3.3
5.0
5.8
1.1
6.9
5.8
3.5
2.9
4.1
6.2
7.2
1.5
9.6
8.0
4.8
4.0
5.6
8.4
9.8
2.2
12
9.7
6.1
5.1
7.3
11.0
12.8
3
14
11
7.7
6.4
8.8
13.2
15.4
4
19
16
11
9.5
12.5
18.8
21.9
5.5
22
18
12
10
15.6
23.4
27.3
7.5
31
26
18
15
23.1
34.7
40.4
11
52
43
25
20
31
46.5
54.3
15
61
51
32
26
38
57
66.5
18.5
67
56
38
32
44
66
77.0
22.0
3AXD00000353783 L
Fuses
Size of copper conductor
gG
UL
Supply
Motor
PE
Class T
(U1, V1, W1)
(U2, V2, W2)
or CC
(600 V)
2
2
2
A
A
mm
AWG
mm
AWG
mm
AWG
10
10
2.5
14
0.75
18
2.5
14
16
20
2.5
14
0.75
18
2.5
14
1)
16/20
25
2.5
10
1.5
14
2.5
10
1)
20/25
30
2.5
10
1.5
14
2.5
10
1)
25/35
35
6
10
2.5
12
6
10
10
10
2.5
14
0.75
18
2.5
14
10
10
2.5
14
0.75
18
2.5
14
10
15
2.5
14
0.75
18
2.5
14
16
15
2.5
12
1.5
14
2.5
12
16
15
2.5
12
1.5
14
2.5
12
16
20
2.5
12
2.5
12
2.5
12
25
30
6
10
6
10
6
10
25
35
6
10
6
10
6
10
63
60
10
8
10
8
10
80
80
16
6
16
6
16
100
100
25
2
25
2
16
10
10
2.5
14
0.75
18
2.5
14
10
10
2.5
14
0.75
18
2.5
14
10
10
2.5
14
0.75
18
2.5
14
10
10
2.5
12
0.75
18
2.5
12
16
15
2.5
12
0.75
18
2.5
12
16
15
2.5
12
1.5
14
2.5
12
16
20
2.5
12
1.5
14
2.5
12
20
25
2.5
12
2.5
12
2.5
12
25
30
6
10
6
10
6
10
35
35
6
8
6
8
6
50
50
10
8
10
8
10
80
80
16
6
16
6
16
100
100
16
4
16
4
16
100
100
25
4
25
4
16
3AXD00000353783 L
During operation (installed for stationary use)
0...2000 m (0...6562 ft) above sea level (with output derating
above 1000 m [3281 ft])
-10...+50 °C (14...122 °F). If the temperature is more than 40 °C
(104 °F), output derating is necessary. No frost permitted.
0...95% without condensation
Requirement
During operation (installed for stationary use)
Contamination levels
No conductive dust permitted
(IEC 60721-3-3: 2002)
Shock (IEC 60068-2-27,
Not permitted
ISTA 1A)
Free fall
Not permitted
Dimensions and weights
Frame
H1
H2
size
mm
in
mm
in
R0
169
6.65
202
7.95
R1
169
6.65
202
7.95
R2
169
6.65
202
7.95
R3
169
6.65
202
7.95
R4
181
7.13
202
7.95
Frame
H4
H5
Frame
size
mm
in
mm
in
size
R0
257
10.12
280
11.02
P
N
R1
257
10.12
280
11.02
R2
257
10.12
282
11.10
hp
R3
260 10.24
299
11.77
R4
270
10.63
320
12.60
0.5
R0
1
R1
IP20 (cabinet) / UL open
1.5
R1
H1
height without fastenings or clamping plate
2
R2
H2
height with fastening and without clamping plate
H3
height with fastenings and clamping plate
3
R2
W
width
D
depth
0.5
R0
IP20 / NEMA 1 (drive with optional MUL-xx kit installed)
H4
height with fastenings and connection box
0.75
R0
H5
height with fastenings, connection box and hood
1
R1
1.5
R1
Free space requirements
2
R1
3
R2
Above
3
R2
mm
in
5
R2
75
3
7.5
R3
10
R4
Markings
15
R4
The applicable markings are shown on the type designation label.
0.5
R0
0.75
R0
1
R1
1.5
R1
2
R1
CE
UL
RCM
3
R1
Declaration of conformity
3
R1
5
R1
The drive is equipped with a Safe torque off function (STO). If you implement,
7.5
R3
start up, use or maintain a system that uses the STO, read and obey the STO
instructions in the drive user's manual.
10
R3
15
R3
20
R4
25
R4
30
R4
Brake
(BRK+, BRK-)
2
mm
AWG
2.5
14
2.5
14
2.5
12
2.5
12
6
12
2.5
14
2.5
14
2.5
14
2.5
12
2.5
12
2.5
12
2.5
12
2.5
12
8
6
10
6
10
8
4
10
8
2.5
14
2.5
14
2.5
14
2.5
12
2.5
12
2.5
12
2.5
12
2.5
12
2.5
12
8
2.5
12
8
6
10
6
10
8
4
10
8
4
10
8
IP20 (cabinet) / UL open
H3
W
D
Weight
mm
in
mm
in
mm
in
kg
lb
239
9.41
70
2.76
161
6.34
1.2
2.6
239
9.41
70
2.76
161
6.34
1.4
3.0
239
9.41
105
4.13
165
6.50
1.8
3.9
236
9.29
169
6.65
169
6.65
3.1
6.9
244
9.61
260
10.24
169
6.65
5.2
11.5
IP20 / NEMA 1
W
D
-
Weight
mm
in
mm
in
-
-
kg
lb
70
2.76
169
6.65
-
-
1.6
3.5
70
2.76
169
6.65
-
-
1.8
3.9
105
4.13
169
6.65
-
-
2.2
4.8
169
6.65
177
6.97
-
-
3.7
8.2
260
10.24
177
6.97
-
-
5.8
12.9
3AXD00000353783 L
Below
Sides
mm
in
mm
in
75
3
0
0
3AXD00000353783 L
EAC
WEEE
EIP
TÜV Nord
„