Installation
Control Box Mounting
1. Locate an area with enough space to mount the
control box and fasten to the wall.
.75 to .875 inch
diameter hole
Control Box may be factory mounted. If so, continue
to the next section.
Hood
As the control box contains the static pressure
Surface
controls, this control box should be mounted in the
space to be controlled. If the control box is mounted
outside of this space, please refer to the Pneumatic
Static Pressure Kit Installation Instructions.
Resistive Temperature Detector(s)
(RTD) Mounting
Lock Washer
Resistive temperature detector(s) may be factory
Octagon
installed. If so, continue to the next section.
Extension
1. Locate flat area(s) at the top interior of the hood
in front of the filters, towards the front of the
hood.
Exhaust Area
Sensor Install
Cut Out Area
Supply Area (optional)
Top View of Exhaust Hood
Top View of Exhaust Hood
Cut a 3/4-inch diameter hole into the top of
the capture tank. Make sure the resistive
temperature detector(s) will not interfere with fire
system nozzles and is not within 12 inches of
light fixtures.
.75 to .875 inch
diameter hole
.75 to .875 inch
diameter hole
Hood
Surface
Hood
Surface
Center the octagon extension over the hole on
the hood surface.
Octagon
Extension
Octagon
Extension
NOTE
1/4 inch Compression Seal
NOTE
Gasket
NOTE
Nut
Octagon Cover
2. Insert the compression seal into the hole from
the inside of the hood, making sure the gasket
is placed on the fitting before inserting it into
the hole. Install the lock washer and 1-1/2 inch
nut on the threaded portion of the compression
seals and tighten securely.
1/4 inch Compression Seal
Temperature
Sensor
Lock Washer
3. Place the octagon box provided over the fitting
on top of the hood, keeping the fitting centered
in the box.
4. Insert the resistive temperature detector (RTD)
Exhaust Area
into compression seal and tighten to 35 ft-lbs.
Sensor Install
Cut Out Area
All field installation and wiring of electrical
equipment must be done to meet NEC and local
Supply Area (optional)
codes.
Top View of Exhaust Hood
1/4 inch Compression Seal
1/4 inch Compression Seal
Gasket
Gasket
Lock Washer
Nut
Lock Washer
Octagon Cover
Nut
Octagon Cover
Exhaust Area
Exhaust Area
Sensor Install
Cut Out Area
Sensor Install
Cut Out Area
Supply Area (optional)
Gasket
Temperature
Sensor
Nut
Octagon Cover
NOTE
Temperature
Sensor
Temperature
Sensor
Vari-Flow Air Management System