Accurex Vari-Flow Manual de instalación, uso y mantenimiento - Página 8

Navegue en línea o descargue pdf Manual de instalación, uso y mantenimiento para Ventilador Accurex Vari-Flow. Accurex Vari-Flow 16 páginas. Air management system

Vari-Flow Connection Checklist
Power to Vari-Flow Cabinet
 C onnect 120 VAC power for controls
(terminals H, N)
 Connect 120 VAC power for hood lights
(terminals H1, N1)
 Connect lights
(terminals HL, N1)
Power to Variable Frequency Drive(s)
 Line power to VFD input terminals L1/L2/L3
 Load power from VFD output terminals T1/T2/T3
Fire System Interface
 M icroswitch Common and Normally Closed
(terminals 34, 35)
Temperature Sensors (installed in hood)
 Temperature Sensor T1 (terminals 16, 17)
*If more than one temperature sensor is used,
wire the following if applicable.
 Temperature Sensor T2 (terminals 18, 19)
 Temperature Sensor T3 (terminals 20, 21)
 Temperature Sensor T4 (terminals 22, 23)
 Temperature Sensor T5 (terminals 24, 25)
 Temperature Sensor T6 (terminals 26, 27)
 Temperature Sensor T7 (terminals 28, 29)
 Temperature Sensor T8 (terminals 30, 31)
Keypad - whether located on hood, hood cabinet, or
wall mounted.
 C onnect provided cable from keypad to
control cabinet.
Make-Up Air Interface
 2 4 VAC Run Enable (terminals 42, 43) to make-up
air (terminals 42, 43)*
 T empering Status (terminals 44, 45) to make-up
air (terminals 44, 45)*
 0 -10 VDC Speed Reference (terminals 46, 47) to
make-up air (terminals 46, 47)*
 If using pressure mode, run tubing to adjacent
room or outside.
*Terminal numbers for Accurex make-up air
units. If using alternate manufacturer's make-up
air unit, consult manufacturer for needed terminal
connections.
Shunt Trip (if used)
 N ormally open set of contacts to be used to shunt
appliances.
Grease Grabber H 2 O Interface (if used)
 G rease Grabber H2O / Vari-Flow interface
(terminals V1, VC)
 K eypad interface (terminals 1, 3, 5, 7, 10, 13 to
terminals 1, 3, 5, 7, 10, 13)
8
Vari-Flow Air Management System

Controller Setup

This section details the process of entering the setup
controls of the programmable logic controller(s)
(PLCs). The controllers are factory set with standard
default values which are shown in the controller
settings table on pages 9-12.
Within the programmable logic controller, factory
set points can be modified to configure the system
for specific functions if necessary. To modify the
parameters, refer to the steps provided.
For a complete list of all settings within the
Controller U1, please refer to the FX15 Vari-Flow
Controller Display tables on pages 9-12.
Controller U1
1. To view factory default settings for the controller,
scroll through the respective controller menus
using the up and down arrow buttons.
2. To modify settings for a Controller U1, press
the escape (ESC) button on the controller to
navigate to the "Accounts" menu and follow the
subsequent steps.
3. Press return while "Accounts" is displayed.
When "User: GFC" appears, press the return
button.
4. Enter the first character of the password
(password is 3637) by using the up and down
arrow buttons. When the appropriate value is
displayed, press return. Continue until the entire
four digit password has been entered.
5. Once the password has been successfully
entered, press ESC and the display will return to
the main menu. Continue to scroll through the
menus using the left and right arrow buttons,
enter a menu by pressing the return button.
Scroll within the menus using the up and down
arrow buttons.
6. To back out of any menu, press the escape (ESC)
button.
NOTE
Up
Left
Right
Down
Return
ESC