7.

Technical Data

7.1

General

Supply voltage
External fuses
Analog input
Analog output
Digital inputs, DI
Digital outputs, DO
Digital
communication
Default settings
Individual settings
Protection class
Humidity
Ambient temperature
Mounting orientation
Varnish
Link cable between
actuator and electron-
ics
Weight
Table 1
1)
Not available for communication via PROFIBUS DP
7.2

Current Consumption of EAN823

PME 120 AN
LME 620 AN
Table 2
6
EAN823
115 V AC (94 V ... 130 V) or
230 V AC (190 V ... 260 V) ;
47.5 ... 63 Hz; 1Ph
0 / 4 ... 20 mA; impedance 50 Ohm
1)
1)
0 / 4 ... 20 mA, electricallly isolated;
max. load resistance 500 Ohm
1)
Logical 0:-3V ... + 5 V or open, electrically isolated
Logical 1:+12 V ...+ 35 V, electrically isolated
1)
Potential-free relay contact, max. 60 V, 150 mA
RS 232 for commissioning and service, optional FSK / HART® or
PROFIBUS DP
Behavior in 0/100% position:
Setpoint function:
Input (setpoint):
Function:
Output (actual value):
Digital inputs:
Digital outputs:
Mounting on vertical mounting plate, cable
glands to the left
2 m... 30 m (max.)
approx. 10 kg
I
115 V
max
1.0 A
1.0 A
EBN853
16 A; slow-blow
Keeping closed with rated torque
Linear;
setpoint = positioning value
4 ... 20 mA
Positioner, parameter: setpoint
4 ... 20 mA
DI 1 switch-over manual/automatic and
v.v., DI 2 / DI 3 manual control +/-
DO 1 ready to operate, DO 2/3 end positi-
on signalling
See data sheet 68-2.40 or on request
IP 66
≤ 95% annual average (condensation permitted)
-25° C ... +55° C
2-component epoxy resin (RAL 9005, black)
approx. 11 kg
I
230 V
max
0.55 A
0.55 A
EBN861
230 V AC (190 V... 260 V);
47.5 ... 63 Hz; 1Ph
35 A fuse
16 A thermal safety cutout
1)
1)
1)
Mounting on vertical mounting
plate, cable glands at the bot-
tom
2 m... 100 m (max.)
approx. 42 kg
I
pos.
each around
40 ... 50% of I
max
1)