Conventional System (Single Transformer)
Terminal
Block
X
RH
W1
SW5 Settings:
Position 1, Not used
Position 2, Not used
Position 3, Not used
Position 4, differential, OFF (0.5°), ON (1.0°)
OFF
ON
¤ For H1 to be active, a plug in setpoint is required in H1 position
9510-0847 Rev C
11-23-09
Common (optional)
Heat System Power (24VAC)
Stage 1 Heating¤
Operating with a common wire connection:
If installing the thermostat with a common wire connection, place the
ENERGY HARVESTING switch in the OFF position. Upon first power
up or following a power failure the thermostat will run under normal
operating conditions within 5 minutes.
Operating without a common wire connection:
If installing the thermostat without a common wire connection, do the
following:
Prior to mounting the thermostat –
Place the ENERGY HARVESTING switch in the ON position.
Place the HEAT switch in the ON position.
At first power up or following a power failure it may take the thermostat
7 to 20 minutes for the power harvesting circuitry to charge before going
into the first heating call.
An optional method of bypassing the 7 to 20 minute wait is to connect
a 9V battery to the sensor board battery terminals.
LED D1 will light once the battery is connected.
When done charging the LED will become dim or go off (approximately
2 minutes).
Remove battery and the thermostat will run under normal operating
conditions within 5 minutes.
While the battery is attached the unit may be tested as stated below.
NOTE: The thermostat will not attempt to control temperature
until the battery is removed.
IMPORTANT NOTICE TO INSTALLERS
To place thermostat in test mode connect a 9 volt battery to sensor
board battery terminals.
If storage capacitors are not charged the LED will come on in the
upper right corner. If the storage capacitors are charged there will be
no light.
NOTE: To test, plug-in setpoints are required.
CONVENTIONAL SYSTEM TEST:
1. Press "C" button.
Heating (W1) will turn on.
2. Press "C" button again.
Heating (W1) will turn off.
3. Test is complete.