correct the interference by one or more of the following
measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.

Important Notes

Read before installation.
Codes: Install in accordance with all local and
national electrical codes.
Alternate wiring methods may be used for the
Class 2 wiring connection. The 2002 National
Electrical Code (Article 725-55) prohibits Class
2 conductors of the -DIM1, -DIMS1, and
-SLVD1 to occupy the same outlet box as the
power conductors. The exception is Part D of
Section 725.55 of the 2002 National Electrical
Code, which allows a device's power conductors
to be installed near (0.25 inch minimum spacing)
associated Class 2 conductors in the same outlet
box. Consult the 2002 National Electrical Code
Handbook and your local electrical inspector
before proceeding.
Do not use the supplied butt-splice connectors if
the Class 2 conductors are to be installed in the
wallbox with the power conductors. Use
approved connectors (supplied by others) to
make Class 2 connections inside the wallbox.
CAUTION
: TO REDUCE THE RISK OF
OVERHEATING AND POSSIBLE DAMAGE
TO OTHER EQUIPMENT, DO NOT INSTALL
TO CONTROL A RECEPTACLE OR A
MOTOR OPERATED APPLIANCE (i.e. BATH
FAN).
Wiring: Use copper wire only. For supply
connections, use wires rated for at least 75°C.
Lamp Type: The -DIM1, -DIMS1, and -SLVD1
are designed for use with permanently installed
incandescent, magnetic low voltage, or tungsten-
halogen only.
Temperature: The -DIM1, -DIMS1, and -SLVD1
are designed to be used where temperatures are
between 32° to 104°F (0° to 40°C).
Wallboxes: Devices mount in standard
wallboxes. For easy installation, Crestron
Installation Guide – DOC. 6250A
CLW-DIM1, DIMS1, & SLVD1(W/A/B)
Multigang Installations
In multigang installations, several controls are grouped
horizontally in one wallbox. For a smooth appearance,
one-piece multigang faceplates (not supplied) can be
installed.
1. When combining controls in a wallbox, remove
Stand Alone Wall Box Dimmer: CLW-DIM1, DIMS1, & SLVD1 • 3
recommends using 3 ½" deep wallboxes. Several
devices can be installed in one wall box
(multigang). This requires the removal of side
sections (refer to diagram on page 4) and the
derating of the dimming device. For a smooth
appearance, one-piece multigang faceplates (not
supplied) can be installed.
Other Switch Devices: Mechanical 3- or 4-way
switches will not work with the -DIM1, -DIMS1,
or -SLVD1.
Spacing: If mounting one device above another,
leave at least 4 ½" vertical space between them.
Low Voltage Applications: Use with core and
coil (magnetic) low voltage transformers only.
Do not use any solid-state electronic low voltage
transformers.
Operation of a low voltage circuit with all lamps
inoperative or removed may result in current
flow in excess of normal levels. To avoid
transformer overheating and premature
transformer failure, Crestron recommends the
following:
Do not operate low voltage circuits
without operative lamps in place.
Replace burned-out lamps as quickly as
possible.
Use transformers that incorporate
thermal protection or fuse transformer
primary windings to prevent
transformer failure due to overcurrent.
inner side sections prior to wiring (refer to the
following figure).