También para Siemens SIMATIC ET 200SP HA: Manual (32 páginas), Manual (50 páginas), Manual (34 páginas), Manual (38 páginas), Manual de equipamiento (50 páginas), Manual de equipamiento (38 páginas), Manual de equipamiento (46 páginas), Manual de equipamiento (42 páginas), Manual de equipamiento (44 páginas), Manual de equipamiento (36 páginas), Manual de equipamiento (38 páginas)

Siemens SIMATIC ET 200SP HA Manual de equipamiento
Installation

4.3 BusAdapter BA 2xFC

PROFINET IO loop-through
2-port switches are integrated in all BusAadapters of ET 200SP HA. These switches allow you
to loop-through the PROFINET IO system from one station to the next.
Number of media interfaces
Avoid a network structure in which there are more than 4 interfaces between electrical and
optical media in a PROFINET IO system between the CPU and any IO device.
From this it follows, for example:
● CPU > Media Interface > IO Device > IO Device > Media Interface > Media Interface > IO
Device > Media Interface > IO Device
Result: Configuration of PROFINET IO system OK
● CPU > Media Interface > Media Interface > IO Device > > Media Interface > Media Interface
> IO Device > > Media Interface > Media Interface > IO Device
Result: Configuration of PROFINET IO system NOT RECOMMENDED
Additional information
● You can find information on the bus cables in the system manual
SIMATIC NET Industrial Ethernet / PROFINET Passive Network Components
support.industry.siemens.com/cs/ww/en/view/84922825)
● Refer to the specifications in the "PROFINET Installation Guide (http://www.profibus.com)".
4.3
BusAdapter BA 2xFC
Introduction
Plug
Front view
4
3
You connect the IO device to the PROFINET IO system via the BusAdapter BA 2×FC with
FastConnect cables.
14
Description
LED LK 1 - Status of Ethernet connection port 1
5
LED LK 2 - Status of Ethernet connection port 2
You can find information on this in section "Diagnostics via LED
displays (Page 29)".
Connection diagram for the PROFINET connectors (view
from below)
Fixing screw
Tightening torque
1
2
BusAdapter for Distributed I/O
Equipment Manual, 09/2019, A5E39261458-AB
(https://