Introduction
1.1 Feature Highlights
Cyber Security Features
Management Tools
Universal Power Supply Options
2
Zero-Packet-Loss™ Technology
Meets IEEE 1613 Class 2 (electric utility substations)
Exceeds IEC 61850-3 (electric utility substations)
Exceeds IEC 61800-3 (variable speed drive systems)
Exceeds IEC 61000-6-2 (generic industrial)
Exceeds NEMA TS-2 (traffic control equipment)
-40 to 85 °C (-40 to 185 °F) operating temperature (no fans)
Failsafe Output Relay: For critical failure or error alarming
Conformal coated printed circuit boards (optional)
Multi-level user passwords
SSH/SSL (128-bit encryption)
Enable/disable ports, MAC based port security
Port based network access control (802.1x)
VLAN (802.1Q) to segregate and secure network traffic
RADIUS centralized password management
SNMPv3 authentication and 56-bit encryption
Web-based, Telnet, CLI management interfaces
SNMP v1/v2/v3 (56-bit encryption)
Remote Monitoring (RMON)
Rich set of diagnostics with logging and alarms
Fully integrated, dual-redundant (optional) power supplies
Universal high-voltage range: 88-300VDC or 85-264VAC
Popular low voltage ranges: 24VDC (10-36VDC), 48VDC (36-59VDC)
Terminal blocks for reliable maintenance free connections
CSA/UL 60950 safety approved to 85 °C (185 °F)
RUGGEDCOM RS1600