6.3 Typical HVAC Applications
The following list is comprised of common HVAC orientated applications, and should provide a useful
starting point for most projects.
#0
-
Default 0-10V Speed Set-point Low Level Control
#1
-
4 Fixed Speeds & Fixed Speed Essential Services Mode
#2
-
0-10V Speed Set-point & Fixed Speed Essential Services Mode
#3
-
Single Zone Stairwell Pressurisation System
#4
-
Two Zone Stairwell Pressurisation System
#5
-
Multi-zone Stairwell using external SEZ220 signal selector
#6
-
Cooling Tower Fan using Internal PID & Hibernation Feature
#7*
-
Cooling Tower Fan with Hibernation & Cond Water Bypass
#8
-
Constant Pressure Control with Fixed Speed ESM (e.g. Multi-zone VAV App)
#9*
-
Single Zone Carpark Ventilation Standalone Solution
#10*
-
Two Zone Carpark Ventilation Standalone Solution
#11*
-
Three Zone Carpark Ventilation Standalone Solution
#12*
-
Condenser Pump Differential Pressure Control (e.g. multiple water cooled DX units)
#13*
-
CHW Pump Constant Flow Control using int PID & Chiller DP Sensor
#14*
-
CHW Pump Constant Flow Control using int PID & Magflow
#15*
-
Refrigerant Compressor (reciprocating) using HI Overload mode
#16*
-
Fieldbus example using BACnet
#17*
-
Fieldbus example using Modbus
* These applications are planned to be released on an on going basis.
Legend
Tan Colour
Notes and read only parameters
Light Green Colour
Quick commissioning parameters
Light Blue Colour
Optional parameters (enhancements), not necessary for every application
Dark Blue Colour
Special parameters
Pink Colour
In most instances do not change
Notes
Some of the parameters mentioned in the following applications can only be accessed via the Expert list.
Ensure you select this when you enter the Parameter menu.
The Technological Units (PID loop) is a new feature of the current Control unit – firmware version 4.4. At
date of compiling this guide, the BOP-2 does not show these units. This is also the case for the IOP,
however a firmware upgrade will be released soon that will enable this feature. So currently the only way to
see these Tech Units is via the fieldbus interface. For this reason it is not necessary to select the
corresponding parameters P595 and P596 if you are only communicating to the drive via the BOP-2.
If you decide to use the Technological Units, there is a sequence that should be followed to enable this
feature: -
1. Set P10 = 5
2. Set P596 = 100 (or the scaling factor recommended in the App sheet)
3. Set P595 = X (e.g. 1 = %, 4 = C, 5 = Pa, etc. - determined by your application)
4. Set P10 = 0
5. Continue with the parameters listed in the chosen application.
For additional information, please refer to the manuals listed in the Website Links section on page 6.