Siemens SIPROTEC T103 Manual - Página 19
Navegue en línea o descargue pdf Manual para Equipamiento industrial Siemens SIPROTEC T103. Siemens SIPROTEC T103 38 páginas.
2.3.4
Selection of Standard Information Numbers In Control Direction
2.3.4.1
System Functions In Control Direction
INF
Semantics
<0>
Initiation of general interrogation
<0>
Time synchronization
2.3.4.2
General Commands In Control Direction
INF
Semantics
<16>
Auto-recloser on/off
<17>
Teleprotection on/off
<18>
Protection on/off
<19>
LED reset
<23>
Activate characteristic 1
<24>
Activate characteristic 2
<25>
Activate characteristic 3
<26>
Activate characteristic 4
2.3.4.3
Generic Functions In Control Direction
INF
Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> General interrogation of generic data
<248> Write entry
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry abort
2.3.5
Basic Application Functions
Test mode
Blocking of monitor direction
Disturbance data
Generic services
7VU68x Redundant T103 Bus mapping
C53000-L2540-C558-1
IEC 60870-5-103 Interoperability
19