Siemens 3NJ6160 Manual de instrucciones - Página 16

Navegue en línea o descargue pdf Manual de instrucciones para Interruptor Siemens 3NJ6160. Siemens 3NJ6160 26 páginas. Plug-in in-line fuse switch-disconnectors

Connection of
size 00
Connection of a sector-
shaped cable
Cable connection depen-
ding on switching device
size and type of connec-
tion
Fig. 5: Size 00, view of 3 terminals, 1 cable connected
Fig. 7: Size 1, view of 3 double terminals,
2 cables connected
3ZX1012-0NJ61-2AN1
Caution!
For size 00, retrofitting of cable terminals is not possible. Where measuring current transfor-
mers are used for size 00, the use of switching devices with cable terminals simplifies con-
nection work. The 10 mm² conductor can be bent double (through 180°).
Fig 3: Connection of 10 mm² cable in terminal of size 00
Fig 4: Positioning a sector-shaped cable in the terminal
Tool: Terminal wrench. Order No.: 3NJ6916-4CA00
All in-line fuse switch-disconnectors can be connected to the cables, either with cable lug or
directly via cable terminals.
Fig. 6: Size 1, view of 3 single terminals,
1 cable connected
Fig. 8: Size 2 and 3, cable lug
17