4 Configuration and Settings
No.
Action
4.
Configure the PROFINET interface of
the drive:
Open the "Properties" of the
1.
drive.
2.
You can set the IP address and
the device name in the
"PROFINET interface" settings.
5.
For data exchange between CPU and
drive, leave the setting at standard
telegram 1 unchanged.
Adding the HMI (optional)
Table 4-3: Adding the HMI
No.
Action
Add the HMI in the "Network view".
1.
2.
Configure an HMI connection
between CPU and HMI.
3.
Then, check the PROFINET
addresses set.
Drehzahlachse mit SINA_SPEED
Entry-ID: 109485727,
V1.0,
06/2017
Remark
Remark
16