Siemens SITRANS L Pointek ULS200 Manual de instrucciones - Página 26
Navegue en línea o descargue pdf Manual de instrucciones para Interruptor Siemens SITRANS L Pointek ULS200. Siemens SITRANS L Pointek ULS200 47 páginas. Ultrasonic non-contacting switch
The outputs can be set to function in the desired mode.
Application
High/Low level switch
High level switch with
two height alarms
Low level switch with
two height alarms
High level switch with
loss of echo alarm
Low level switch with
loss of echo alarm
Pump down control with
low level alarm
Pump down control with
high level alarm
Pump up control with
low level alarm
Pump up control with
high level alarm
Pump down control with
loss of echo alarm
Pump up control with
loss of echo alarm
Pump up control and
Pump down control
Dual pump down con-
trol
Dual pump up control
*Factory setting
Alarm: the relay de-energizes to set the alarm 'ON'.
Control or pump: the relay energizes to set the device 'ON'.
26
Function
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Relay 1
High alarm
High alarm
Low alarm
High alarm
Low alarm
Pump down
Pump down
Pump up
Pump up
Pump down
Pump up
Pump down
Pump down
Pump up
Operating Instructions, 01/2019, A5E32268616-AB
Relay 2
Low alarm
High alarm
Low alarm
LOE alarm
LOE alarm
Low alarm
High alarm
Low alarm
High alarm
LOE alarm
LOE alarm
Pump up
Pump down
Pump up
Pointek ULS200