Siemens SITRANS LVL200E Manual de instrucciones - Página 23

Navegue en línea o descargue pdf Manual de instrucciones para Interruptor Siemens SITRANS LVL200E. Siemens SITRANS LVL200E 40 páginas. Vibrating switches
También para Siemens SITRANS LVL200E: Manual de instrucciones (44 páginas), Manual de instrucciones (16 páginas), Manual de instrucciones (40 páginas)

Siemens SITRANS LVL200E Manual de instrucciones
Reaction when malfunc-
tions occur
Failure reasons
Fault rectification
Checking the switching
signal
SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH
7 Maintenance and fault rectification

7.1 Maintenance

If the instrument is used properly, no special maintenance is required
in normal operation.

7.2 Rectify faults

The operator of the system is responsible for taking suitable measures
to remove interferences.
SITRANS LVL200E offers maximum reliability. Nevertheless, faults
can occur during operation. These may be caused by the following, e.
g.:
Sensor
l
Process
l
Voltage supply
l
Signal processing
l
The first measure to be taken is to check the output signal. In many
cases, the causes can be determined this way and the faults rectified.
Error
SITRANS LVL200E
signals "covered" when
the vibrating element is
not submerged (overfill
protection)
SITRANS LVL200E
signals "uncovered"
when the vibrating ele-
ment is submerged (dry
run protection)
7 Maintenance and fault rectification
Cause
Operating voltage too
low
Electronics defective
Removal
Check operating voltage
Press the mode switch. If
the instrument then
changes the mode, the
vibrating element may be
covered with buildup or
mechanically damaged.
Should the switching
function in the correct
mode still be faulty, re-
turn the instrument for
repair.
Press the mode switch. If
the instrument then does
not change the mode,
the electronics module is
defective. Exchange the
electronics module.
23