Install Second BBD43 Unit (DLE-48 Only)
DLE-48 requires a second BBD43 installed to ensure
sufficient lighting in an emergency situation. The DLE-
48 luminaire contains a second wiring compartment,
located on the opposite end of the luminaire sensor (see
Identifying Emergency Light Bar & BBD43 Placement) to
accommodate the second BBD43 unit.
To install the second unit, repeat Steps One through Five on
the opposite end of the luminaire.
Wiring configuration and positioning will appear to be
Note:
an inverted variation of the illustrations in this document.
Refer to Understanding DLE Luminaire Wiring
Configurations for details.
Connect to Facility Power
Once you've made all BBD43 power and data connections,
connect the luminaire to facility power.
Battery Test Method
You must connect the luminaire to facility power in order to
test the BBD43 battery.
Press and hold the TEST button on the BBD43 – for no
more than 2 seconds – until the LED status indicator blinks
(alternating red/green), and then release (Illustration 14).
After approximately 15-30 seconds, the indicator will blink
GREEN three times to verify that the battery is working
properly. Otherwise, if the indicator blinks RED three times
(indicating a connection issue), check all connections and then
run the test again.
Refer to the table below for more information on
indicator readouts:
LED
State
Charging
Slowly flash GREEN
Emergency
Constant RED
Error
Quickly flash RED
Standby
Constant GREEN
Test
Alternate RED and GREEN
Digital Lumens
374 Congress Street
Suite 600
Boston, MA 02210 USA
Phone +1 617 723 1200
www.digitallumens.com
INSTALLATION INSTRUCTIONS
Post-Installation
Before servicing the luminaire or BBD43 unit
Disconnect facility power to the luminaire.
On the luminaire, remove the sensor cover, and then press
and hold the RESET button for 10 seconds
(Illustration 15).
Verify the LED status indicators on both the luminaire
sensor and the BBD43 unit are not lit, and that the
luminaire is not emitting light.
On the BBD43, remove the outer access cover (see Step
Five) and disconnect the battery.
Use a #2 Phillips
screwdriver to remove the screw from
®
the bottom retention hook on the BBD43 unit.
Disconnect power and data cables between the luminaire
and BBD43, in reverse order of installation (see Step Two).