Addressing external operating panels: is only necessary if there are 2 external operating
panels:
Scratch away the etched track on the place indicated on operating panel 2 in order to change its
address from 1 to 2.

12 Connecting the optional module

12.1 Relay PCB

An optional PCB with 8 freely-configurable relays can be plugged into the control panel.
The relay PCB is attached to the main PCB with 2 self-adhesive spacers.
The relay contacts are 30 V / 1 A.
The PCB is connected to the main PCB at the Extension connectors.
The functions of the additional relays are programmed via the CMPlus.exe program.
See CMPlus.exe Help for full configuration instructions.