Argo AEI835SH Datos técnicos y manual de servicio - Página 11

Navegue en línea o descargue pdf Datos técnicos y manual de servicio para Aire acondicionado Argo AEI835SH. Argo AEI835SH 18 páginas. Split system air conditioner

4. REFRIGERANT FLOW DIAGRAM

Outdoor Unit:
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this
air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation,
both tubes must be well insulated with a proper insulation material.
The thickness of the insulation should be a min. 8mm.
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve
because it can cause the tube to break or crack.
AEI826SH
AEI835SH
Indoor Unit:
11
AWI8826HL(B)
AWI8835HL(B)
Outdoor Unit
Indoor Unit