finder 8A Series Manual de inicio rápido - Página 6

Navegue en línea o descargue pdf Manual de inicio rápido para Relés finder 8A Series. finder 8A Series 8 páginas. Programmable logic relays

8A
8A SERIES
Programmable Logic Relays
SERIES

Front view

1
7
4
Contact specification
F 8A - Electrical life (AC) v contact current
H
6
2
6
8
5
3
Supply terminals
1
12...24 V DC, Split terminals to facilitate wiring.
Input terminals
2
I1...I8 digital/analog (0...10 V) input configurable via IDE.
Output terminals
3
1...4 Output relay, 10 A 250 V AC, NO contact.
LED Status
4
1...4 LED Status configurable via IDE.
For exemple for 1...4 output relay LED ON = Contact CLOSE.
LED Ethernet port status
5
Status of ETH connection.
Modbus RS485 Port
6
Terminals for Modbus over RS485 protocol.
HARDWARE RESET
7
Button for hardware reset. BE CAREFUL. Press the 'RESET'
button with the tip of a small non-metallic insulated tool.
Programmable USER button
8
Button configurable via IDE by user, according to application
(ex. RUN/STOP, ON/OFF, BLE pair).
H 8A - Maximum DC1 breaking capacity
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100 · 10
expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC voltage (V)
3
can be