Crowcon Detective Net Manual de consulta rápida - Página 2

Navegue en línea o descargue pdf Manual de consulta rápida para Detectores de gas Crowcon Detective Net. Crowcon Detective Net 3 páginas.

Crowcon Detective Net Manual de consulta rápida
Setting Up a Simple Wireless Network
Turn On Devices
Press and hold left button until all LED's scroll from left to
X
right.
Reset Devices
Once powered, press and hold left button for 3 seconds.
X
If device previously configured as a slave, LED 1 will flash 3
X
times to indicate a successful reset.
If device previously configured as a master, LED 1 and LED 4
X
will flash 3 times to indicate a successful reset.
Toggle Devices (Slave to Master/Master to Slave)
A network requires just one master device, to toggle between
master and slave, proceed as follows:
Hold right button for 3 seconds.
X
If toggling from slave to master LED 4 will flash 3 times.
X
If toggling from master to slave LED 1 will flash 3 times.
X
Place Master Device In Learn Mode
Once devices are powered and reset, select the master
X
device.
Double click right button to enter learn mode.
X
LED 1 will continuously flash red and LED 4 will flash green.
X
Learn Slave Device to Master
Select the slave device place 1m apart from master device.
X
Double click right button to enter learn mode.
X
LED 1 will continuously flash red and device will learn
X
automatically.
Once complete LED 1 turns off.
X
LED 2 will flash green to indicate the slave is connected to
X
the master.
Repeat this process for all other slaves to be connected to
X
the network.